Division 3.1 Where the fan is supplied as a ‘final assembly’, measure the gas power and the electric input power of the fan at its optimum energy efficiency point:

United Kingdom

Original text. Later amendments are not shown.

  1. (a)

    where the fan does not include a variable speed drive, calculate the overall efficiency using the following equation:

    ηe = Pu(s) / Pe

    where:

    • ηe is the overall efficiency;

    • Pu(s) is the fan gas power, determined according to point 3.3, of the fan when it is operating at its optimal energy efficiency point;

    • Pe is the power measured at the mains input terminals to the motor of the fan when the fan is operating at its optimal energy efficiency point;

  2. (b)

    where the fan includes a variable speed drive, calculate the overall efficiency using the following equation:

    ηe = (Pu(s) / Ped) · Cc

    where:

    • ηe is the overall efficiency;

    • Pu(s) is the fan gas power, determined according to point 3.3, of the fan when it is operating at its optimal energy efficiency point;

    • Ped is the power measured at the mains input terminals to the variable speed drive of the fan when the fan is operating at its optimal energy efficiency point;

    • Cc is a part load compensation factor as follows:

      • for a motor with a variable speed drive and Ped ≥ 5 kW, then Cc = 1,04,

      • for a motor with a variable speed drive and Ped < 5 kW, then Cc = – 0,03 ln(Ped) + 1,088.