Annex VII Measurements and calculations
United Kingdom
Table 1
Bin number (j), outdoor temperature (Tj) in °C and number of hours per bin (hj) for the cooling season and for heating seasons ‘average’, ‘warmer’ and ‘colder’. ‘db’ = dry bulb temperature
| COOLING SEASON | HEATING SEASON | |||||||
|---|---|---|---|---|---|---|---|---|
| Average | Warmer | Colder | ||||||
| j# | Tj°C | hjh | j# | Tj°C | hjAh | hj Wh | hjCh | |
| db | db | |||||||
| 1 | 17 | 205 | 1 to 8 | – 30 to – 23 | 0 | 0 | 0 | |
| 2 | 18 | 227 | 9 | –22 | 0 | 0 | 1 | |
| 3 | 19 | 225 | 10 | –21 | 0 | 0 | 6 | |
| 4 | 20 | 225 | 11 | –20 | 0 | 0 | 13 | |
| 5 | 21 | 216 | 12 | –19 | 0 | 0 | 17 | |
| 6 | 22 | 215 | 13 | –18 | 0 | 0 | 19 | |
| 7 | 23 | 218 | 14 | –17 | 0 | 0 | 26 | |
| 8 | 24 | 197 | 15 | –16 | 0 | 0 | 39 | |
| 9 | 25 | 178 | 16 | –15 | 0 | 0 | 41 | |
| 10 | 26 | 158 | 17 | –14 | 0 | 0 | 35 | |
| 11 | 27 | 137 | 18 | –13 | 0 | 0 | 52 | |
| 12 | 28 | 109 | 19 | –12 | 0 | 0 | 37 | |
| 13 | 29 | 88 | 20 | –11 | 0 | 0 | 41 | |
| 14 | 30 | 63 | 21 | –10 | 1 | 0 | 43 | |
| 15 | 31 | 39 | 22 | –9 | 25 | 0 | 54 | |
| 16 | 32 | 31 | 23 | –8 | 23 | 0 | 90 | |
| 17 | 33 | 24 | 24 | –7 | 24 | 0 | 125 | |
| 18 | 34 | 17 | 25 | –6 | 27 | 0 | 169 | |
| 19 | 35 | 13 | 26 | –5 | 68 | 0 | 195 | |
| 20 | 36 | 9 | 27 | –4 | 91 | 0 | 278 | |
| 21 | 37 | 4 | 28 | –3 | 89 | 0 | 306 | |
| 22 | 38 | 3 | 29 | –2 | 165 | 0 | 454 | |
| 23 | 39 | 1 | 30 | –1 | 173 | 0 | 385 | |
| 24 | 40 | 0 | 31 | 0 | 240 | 0 | 490 | |
| 32 | 1 | 280 | 0 | 533 | ||||
| 33 | 2 | 320 | 3 | 380 | ||||
| 34 | 3 | 357 | 22 | 228 | ||||
| 35 | 4 | 356 | 63 | 261 | ||||
| 36 | 5 | 303 | 63 | 279 | ||||
| 37 | 6 | 330 | 175 | 229 | ||||
| 38 | 7 | 326 | 162 | 269 | ||||
| 39 | 8 | 348 | 259 | 233 | ||||
| 40 | 9 | 335 | 360 | 230 | ||||
| 41 | 10 | 315 | 428 | 243 | ||||
| 42 | 11 | 215 | 430 | 191 | ||||
| 43 | 12 | 169 | 503 | 146 | ||||
| 44 | 13 | 151 | 444 | 150 | ||||
| 45 | 14 | 105 | 384 | 97 | ||||
| 46 | 15 | 74 | 294 | 61 | ||||
| Total | 2 602 | 4 910 | 3 590 | 6 446 | ||||
Table 2
Standard rating conditions, temperatures in ‘dry bulb’ air temperature (‘wet bulb’ indicated in brackets)
In case of single ducts, the condensor (evaporator) when cooling (heating), is not supplied with outdoor air, but indoor air. | |||
| Appliance | Function | Indoor air temperature(°C) | Outdoor air temperature(°C) |
|---|---|---|---|
| air conditioners, excluding single duct | cooling | 27 (19) | 35 (24) |
| heating | 20 (max. 15) | 7(6) | |
| single duct | cooling | 35 (24) | 35 (24)f1 |
| heating | 20 (12) | 20 (12) | |
Table 3
Reference design conditions, temperatures in ‘dry bulb’ air temperature (‘wet bulb’ indicated in brackets)
| Function / season | Indoor air temperature(°C) | Outdoor air temperature(°C) | Bivalent temperature(°C) | Operating limit temperature(°C) |
|---|---|---|---|---|
| Tin | Tdesignc/Tdesignh | Tbiv | Tol | |
| cooling | 27 (19) | Tdesignc = 35 (24) | n.a. | n.a. |
| heating / Average | 20 (15) | Tdesignh = – 10 (– 11) | max. 2 | max. – 7 |
| heating / Warmer | Tdesignh = 2 (1) | max. 7 | max. 2 | |
| heating / Colder | Tdesignh = – 22 (– 23) | max. – 7 | max. – 15 |
Table 4
Operational hours per type of appliance per functional mode to be used for calculation of electricity consumption
| Type of appliance / functionality (if applicable) | Unit | Heating season | On mode | Thermostat-off mode | Standby mode | Off mode | Crankcase heater mode | |
|---|---|---|---|---|---|---|---|---|
| cooling: HCEheating: HHE | HTO | HSB | HOFF | HCK | ||||
| Air conditioners, except double ducts and single duct | ||||||||
| Cooling mode, if appliance offers cooling only | h/annum | 350 | 221 | 2 142 | 5 088 | 7 760 | ||
| Cooling and heating modes, if appliance offers both modes | Cooling mode | h/annum | 350 | 221 | 2 142 | 0 | 2 672 | |
| Heating mode | h/annum | Average | 1 400 | 179 | 0 | 0 | 179 | |
| Warmer | 1 400 | 755 | 0 | 0 | 755 | |||
| Colder | 2 100 | 131 | 0 | 0 | 131 | |||
| Heating mode, if appliance offers heating only | h/annum | Average | 1 400 | 179 | 0 | 3 672 | 3 851 | |
| Warmer | 1 400 | 755 | 0 | 4 345 | 4 476 | |||
| Colder | 2 100 | 131 | 0 | 2 189 | 2 944 | |||
| Double duct air conditioner | cooling: HCEheating: HHE | HTO | HSB | HOFF | HCK | |||
| Cooling mode, if appliance offers cooling only | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
| Cooling and heating modes, if appliance offers both modes | Cooling mode | h/60 min | 1 | n/a | n/a | n/a | n/a | |
| Heating mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
| Heating mode, if appliance offers heating only | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
| Single duct air conditioner | cooling: HCEheating: HHE | |||||||
| Cooling mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
| Heating mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
- 1Division 1
- 2The determination of the seasonal energy consumption and seasonal energy efficiency ratio (SEER) and seasonal coefficient of performance (SCOP) shall take into account:
- 3Division 3
- 4Division 4
- 5Division 5
Annotations
Footnotes
- f1
In case of single ducts, the condensor (evaporator) when cooling (heating), is not supplied with outdoor air, but indoor air.