# Commission Regulation (EU) No 813/2013 of 2 August 2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for space heaters and combination heaters (Text with EEA relevance), Division 3: REQUIREMENTS FOR SOUND POWER LEVEL

Extent: E+W+S+N.I.

From 26 September 2015 the sound power level of heat pump space heaters and heat pump combination heaters shall not exceed the following values:
Rated heat output ≤ 6 kW
Rated heat output > 6 kW and ≤ 12 kW
Rated heat output > 12 kW and ≤ 30 kW
Rated heat output > 30 kW and ≤ 70 kW
Sound power level (LWA ), indoors
Sound power level (LWA ), outdoors
Sound power level (LWA ), indoors
Sound power level (LWA ), outdoors
Sound power level (LWA ), indoors
Sound power level (LWA ), outdoors
Sound power level (LWA ), indoors
Sound power level (LWA ), outdoors
60 dB
65 dB
65 dB
70 dB
70 dB
78 dB
80 dB
88 dB

---