Division 2 From 1 January 2018:
United Kingdom
-
SEC, calculated for average climate, shall be no more than – 20 kWh/(m2.a).
-
Non-ducted units including ventilation units intended to be equipped with one duct connection on either supply or extract air side shall have a maximum LWA of 40 dB.
-
All VUs, except dual use units, shall be equipped with a multi-speed drive or variable speed drive.
-
All BVUs shall have a thermal by-pass facility.
-
Ventilation units with a filter shall be equipped with a visual filter change warning signal.