Division 1 From 1 January 2016:
United Kingdom
-
All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive.
-
All BVUs shall have a HRS.
-
The HRS shall have a thermal by-pass facility.
-
The minimum thermal efficiency ηt_nrvu of all HRS except run-around HRS in BVUs shall be 67 % and the efficiency bonus E = (ηt_nrvu – 0,67) * 3 000 if the thermal efficiency ηt_nrvu is at least 67 %, otherwise E = 0.
-
The minimum thermal efficiency ηt_nrvu of run-around HRS in BVUs shall be 63 % and the efficiency bonus E = (ηt_nrvu – 0,63) * 3 000 if the thermal efficiency ηt_nrvu is at least 63 %, otherwise E = 0.
-
The minimum fan efficiency for UVUs (ηνu ) is
-
6,2 % * ln(P) + 35,0 % if P ≤ 30 kW and
-
56,1 % if P > 30 kW.
-
-
The maximum internal specific fan power of ventilation components (SFPint_limit ) in W/(m3/s) is
-
for a BVU with run-around HRS
-
1 700 + E – 300 * qnom /2 – F if qnom < 2 m3/s and
-
1 400 + E – F if qnom ≥ 2 m3/s;
-
-
for a BVU with other HRS
-
1 200 + E – 300 * qnom /2 – F if qnom < 2 m3/s and
-
900 + E – F if qnom ≥ 2 m3/s;
-
-
250 for an UVU intended to be used with a filter.
-