Division 1 From 1 January 2016:

United Kingdom

Original text. Later amendments are not shown.

  • All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive.

  • All BVUs shall have a HRS.

  • The HRS shall have a thermal by-pass facility.

  • The minimum thermal efficiency ηt_nrvu of all HRS except run-around HRS in BVUs shall be 67 % and the efficiency bonus E = (ηt_nrvu – 0,67) * 3 000 if the thermal efficiency ηt_nrvu is at least 67 %, otherwise E = 0.

  • The minimum thermal efficiency ηt_nrvu of run-around HRS in BVUs shall be 63 % and the efficiency bonus E = (ηt_nrvu – 0,63) * 3 000 if the thermal efficiency ηt_nrvu is at least 63 %, otherwise E = 0.

  • The minimum fan efficiency for UVUs (ηνu ) is

    • 6,2 % * ln(P) + 35,0 % if P ≤ 30 kW and

    • 56,1 % if P > 30 kW.

  • The maximum internal specific fan power of ventilation components (SFPint_limit ) in W/(m3/s) is

    • for a BVU with run-around HRS

      • 1 700 + E – 300 * qnom /2 – F if qnom < 2 m3/s and

      • 1 400 + E – F if qnom ≥ 2 m3/s;

    • for a BVU with other HRS

      • 1 200 + E – 300 * qnom /2 – F if qnom < 2 m3/s and

      • 900 + E – F if qnom ≥ 2 m3/s;

    • 250 for an UVU intended to be used with a filter.