Annex VIII Calculation of the specific energy consumption requirement

United Kingdom

Original text. Later amendments are not shown.

The specific energy consumption SEC is calculated with the following equation:

SEC = t a × pef × q net × MISC × CTRL x × SPI − t h × ΔΤ h × η – 1 h × c air × q ref − q net × CTRL × MISC × 1 − η t + Q defr

where:

  • SEC is Specific Energy Consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/(m2.a)];

  • ta is annual operating hours [h/a];

  • pef is primary energy factor for electric power generation and distribution [-];

  • qnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];

  • MISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];

  • CTRL is ventilation control factor [-];

  • x is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];

  • SPI is Specific Power Input [kW/(m3/h)];

  • th is total hours heating season [h];

  • ΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3K correction for solar and internal gains [K];

  • ηh is the average space heating efficiency [-];

  • cair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];

  • qref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];

  • ηt is the thermal efficiency of heat recovery [-];

  • Qdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.

    Q defr = t defr × ΔΤ defr × c air × q net × pef ,

    where

    • tdefr is the duration of defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a], and

    • ΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.

    Qdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchanger is Qdefr = 0.

SPI and ηt are values derived from tests and calculation methods.

Other parameters and their defaults are given in Table 1.

Table 1

SEC calculation parameters

Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr * Δtdefr * cair * qnet * pef. For unidirectional units or unit with regenerative heat exchanger is Qdefr = 0

general typology MISC
Ducted units 1,1
Non-ducted units 1,21
ventilation control CTRL
Manual control (no DCV) 1
Clock control (no DCV) 0,95
Central demand control 0,85
Local demand control 0,65
motor & drive x-value
on/off & single speed 1
2-speed 1,2
multi-speed 1,5
variable speed 2
Climate th in h ΔΤh in K tdefr in h ΔΤdefr in K Qdefr f1in kWh/a.m2
Cold 6 552 14,5 1 0035,2 5,82
Average 5 112 9,5 1682,4 0,45
Warm 4 392 5 ———
Defaults value
specific heat capacity of air, cair in kWh/(m3K) 0,000344
net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 1,3
reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 2,2
annual operating hours, ta in h 8760
primary energy factor electric power generation & distribution, pef 2,5
space heating efficiency, ηh 75 %

Annotations

Footnotes

f1

Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr * Δtdefr * cair * qnet * pef. For unidirectional units or unit with regenerative heat exchanger is Qdefr = 0