Annex VIII Calculation of the specific energy consumption requirement
United Kingdom
The specific energy consumption SEC is calculated with the following equation:
where:
-
SEC is Specific Energy Consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/(m2.a)];
-
ta is annual operating hours [h/a];
-
pef is primary energy factor for electric power generation and distribution [-];
-
qnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];
-
MISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];
-
CTRL is ventilation control factor [-];
-
x is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];
-
SPI is Specific Power Input [kW/(m3/h)];
-
th is total hours heating season [h];
-
ΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3K correction for solar and internal gains [K];
-
ηh is the average space heating efficiency [-];
-
cair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];
-
qref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];
-
ηt is the thermal efficiency of heat recovery [-];
-
Qdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.
,
where
-
tdefr is the duration of defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a], and
-
ΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.
Qdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchanger is Qdefr = 0.
-
SPI and ηt are values derived from tests and calculation methods.
Other parameters and their defaults are given in Table 1.
Table 1
SEC calculation parameters
| Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr * Δtdefr * cair * qnet * pef. For unidirectional units or unit with regenerative heat exchanger is Qdefr = 0 | |||||
| general typology | MISC | ||||
|---|---|---|---|---|---|
| Ducted units | 1,1 | ||||
| Non-ducted units | 1,21 | ||||
| ventilation control | CTRL | ||||
| Manual control (no DCV) | 1 | ||||
| Clock control (no DCV) | 0,95 | ||||
| Central demand control | 0,85 | ||||
| Local demand control | 0,65 | ||||
| motor & drive | x-value | ||||
| on/off & single speed | 1 | ||||
| 2-speed | 1,2 | ||||
| multi-speed | 1,5 | ||||
| variable speed | 2 | ||||
| Climate | th in h | ΔΤh in K | tdefr in h | ΔΤdefr in K | Qdefr f1in kWh/a.m2 |
| Cold | 6 552 | 14,5 | 1 003 | 5,2 | 5,82 |
| Average | 5 112 | 9,5 | 168 | 2,4 | 0,45 |
| Warm | 4 392 | 5 | — | — | — |
| Defaults | value | ||||
| specific heat capacity of air, cair in kWh/(m3K) | 0,000344 | ||||
| net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 | 1,3 | ||||
| reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 | 2,2 | ||||
| annual operating hours, ta in h | 8760 | ||||
| primary energy factor electric power generation & distribution, pef | 2,5 | ||||
| space heating efficiency, ηh | 75 % | ||||
Annotations
Footnotes
- f1
-
Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr * Δtdefr * cair * qnet * pef. For unidirectional units or unit with regenerative heat exchanger is Qdefr = 0