  "heading": "The specific energy consumption (SEC) is calculated using the following equation:",
  "text": "SEC = t a × pef × q net × MISC × CTRL x × SPI − t h × ΔΤ h × η – 1 h × c air × q ref − q net × CTRL × MISC × 1 − η t + Q defr\nwhere:\nSEC is the specific energy consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/m2.a];\nta is annual operating hours [h/a];\npef is the primary energy factor for electric power generation and distribution [-];\nqnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];\nMISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];\nCTRL is the ventilation control factor [-];\nx is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];\nSPI is specific power input [kW/(m3/h)];\nth is total hours heating season [h];\nΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3 K correction for solar and internal gains [K];\nηh is the average space heating efficiency [-];\ncair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];\nqref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];\nηt is the thermal efficiency of heat recovery [-];\nQdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.\nQ defr = t defr × ΔΤ defr × c air × q net × pef ,\nwhere:\ntdefr is the duration of the defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a]; and\nΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.\nQdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchangers, Qdefr = 0.\nSPI and ηt are values derived from tests and calculation methods.\nOther parameters and their defaults are given in Table 1. The SEC for label classification is based on the ‘average’ climate.",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eur/2014/1254/annex/VIII/division/1",
    "retrieved_at": "2026-11-01T14:47:08.245510+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}