  "url": "https://openlegislation.uk/eu-regulation-2014-548/annex-I/division-1",
  "json_url": "https://openlegislation.uk/eu-regulation-2014-548/annex-I/division-1.json",
  "legislation": "eur/2014/548",
  "legislation_title": "Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers",
  "legislation_url": "https://openlegislation.uk/eu-regulation-2014-548",
  "path": "annex/I/division/1",
  "kind": "division",
  "number": "1",
  "heading": "Minimum energy performance or efficiency requirements for medium power transformers",
  "text": "Medium power transformers shall comply with the maximum allowed load and no-load losses or the Peak Efficiency Index (PEI) values set out in Tables I.1 to I.5, excluding medium power pole-mounted transformers, which shall comply with the maximum allowed load and no load losses values set out in Table I.6.\nAs of the date of application of Tier 2 requirements ( 1 July 2021 ), when the one-to-one replacement of an existing medium power transformer entails disproportionate costs associated with their installation, the replacement transformer is, exceptionally, only required to meet Tier 1 requirements for the given rated power.\nIn this respect, installation costs are disproportionate if the costs of the replacement of the complete substation housing the transformer and/or the acquisition or rental of additional floor space are higher than the net present value of the additional avoided electricity losses (tariffs, taxes and levies excluded) of a Tier 2 compliant replacement transformer over its normally expected service life. The net present value shall be calculated based on capitalised loss values using widely accepted social discount rates .\nIn this case, the manufacturer, importer, or authorised representative shall include in the technical documentation of the replacement transformer the following information:\nAddress and contact details of the commissioner of the replacement transformer\nThe station where the replacement transformer is to be installed. This shall be unequivocally identified by either a specific location or a specific installation type (e.g., station or cabin model)\nThe technical and/or economic justification of the disproportionate cost to install a transformer that is only Tier 1 compliant instead of a Tier 2 compliant one. If the transformers(s) were commissioned by a tendering process, all the necessary information regarding the analysis of bids and the award decision shall be provided.\nIn the above cases, the manufacturer, importer or authorised representative shall notify the competent national market surveillance authorities.",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "F",
      "label": "F1",
      "text": "Inserted by Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance)."
    },
    {
      "type": "footnote",
      "label": "f1",
      "text": "The European Commission Better Regulation Toolbox suggest using a value of 4 % for the social discount rate https://ec.europa.eu/info/sites/info/files/file_import/better-regulation-toolbox-61_en_0.pdf"
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eur/2014/548/annex/I/division/1",
    "retrieved_at": "2026-11-01T14:47:38.642843+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}