Division 1.2 Requirements for medium power transformers with rated power > 3 150 kVA

United Kingdom

Original text. Later amendments are not shown.

Table I.4: Minimum Peak Efficiency Index (PEI) values for liquid immersed medium power transformers

Rated Power (kVA)Tier 1 (1 July 2015)Tier 2 (1 July 2021)
Minimum Peak Efficiency Index (%)
3 150 < Sr ≤ 4 00099,46599,532
5 00099,48399,548
6 30099,51099,571
8 00099,53599,593
10 00099,56099,615
12 50099,58899,640
16 00099,61599,663
20 00099,63999,684
25 00099,65799,700
31 50099,67199,712
40 00099,68499,724

Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.4 shall be calculated by linear interpolation.

Table I.5: Minimum Peak Efficiency Index (PEI) values for dry type medium power transformers

Rated Power (kVA)Tier 1 (1 July 2015)Tier 2 (1 July 2021)
Minimum Peak Efficiency Index (%)
3 150 < Sr ≤ 4 00099,34899,382
5 00099,35499,387
6 30099,35699,389
8 00099,35799,390
≥ 10 00099,35799,390

Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.5 shall be calculated by linear interpolation.

Notes on Division 1

Textual amendments

F1

Inserted by Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance).

Footnotes

f1

The European Commission Better Regulation Toolbox suggest using a value of 4 % for the social discount rate

https://ec.europa.eu/info/sites/info/files/file_import/better-regulation-toolbox-61_en_0.pdf