  "url": "https://openlegislation.uk/eu-regulation-2014-548/annex-I/division-1/division-1.4",
  "json_url": "https://openlegislation.uk/eu-regulation-2014-548/annex-I/division-1/division-1.4.json",
  "legislation": "eur/2014/548",
  "legislation_title": "Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers",
  "legislation_url": "https://openlegislation.uk/eu-regulation-2014-548",
  "path": "annex/I/division/1/division/1.4",
  "kind": "division",
  "number": "1.4",
  "heading": "For the one-to-one replacement of existing medium power pole-mounted transformers with power ratings between 25 kVA and 400 kVA, the applicable maximum levels of load and no-load losses are not the ones in Tables I.1 and I.2, but those in Table I.6 below. Maximum allowable losses for kVA ratings other than those explicitly mentioned in Table I.6 shall be obtained by linear interpolation or extrapolation. The correction factors for special combinations of winding voltages indicated in Tables I.3a and I.3b are also applicable.",
  "text": "For the one-to-one replacement of existing medium power pole-mounted transformers, the manufacturer, importer or authorised representative shall include in the technical documentation of the transformer the following information:\nthe address and contact details of the commissioner of the replacement transformer;\nthe station where the replacement transformer is to be installed. This shall be unequivocally identified either by a specific location or an specific installation type (e.g. technical description of the pole).\nIn the above cases, the manufacturer, importer or authorised representative shall notify the competent national market surveillance authorities.\nWith regard to the installation of new pole-mounted transformers, it is the requirements in Tables I.1 and I.2, in conjunction with Tables I.3a and I.3b where justified, which are applicable.\nTable I.6: Maximum load and no-load losses (in W) for medium power liquid immersed pole-mounted transformers\nMaximum allowable losses for kVA ratings that fall in between the ratings given in Table I.6 shall be obtained by linear interpolation.\nTier 1 (1 July 2015)\nTier 2 (1 July 2021)\nRated Power (kVA)\nMaximum load losses (in W)\nMaximum no-load losses (in W)\nMaximum load losses (in W)\nMaximum no-load losses (in W)\n25\nCk (900)\nAo (70)\nBk (725)\nAo (70)\n50\nCk (1 100)\nAo (90)\nBk (875)\nAo (90)\n100\nCk (1 750)\nAo (145)\nBk (1 475)\nAo (145)\n160\nCk + 32 % (3 102)\nCo (300)\nCk + 32 % (3 102)\nCo – 10 % (270)\n200\nCk (2 750)\nCo (356)\nBk (2 333)\nBo (310)\n250\nCk (3 250)\nCo (425)\nBk (2 750)\nBo (360)\n315\nCk (3 900)\nCo (520)\nBk (3 250)\nBo (440)",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "F",
      "label": "F1",
      "text": "Substituted by Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers (Text with EEA relevance)."
    },
    {
      "type": "footnote",
      "label": "f1",
      "text": "Maximum allowable losses for kVA ratings that fall in between the ratings given in Table I.6 shall be obtained by linear interpolation."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eur/2014/548/annex/I/division/1/division/1.4",
    "retrieved_at": "2026-11-01T14:47:38.642843+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}