Division 2 For establishing the values of annual energy consumption and energy efficiency index for professional refrigerated storage cabinets, measurements shall be carried out under the following conditions:

United Kingdom

Original text. Later amendments are not shown.

  • The temperature of test packages shall be between – 1 °C and 5 °C for chilled cabinets and lower than – 15 °C for frozen cabinets.

  • The ambient conditions shall correspond to climate class 4 as detailed in Table 3, except for light-duty cabinets, which shall be tested in ambient conditions corresponding to climate class 3. Adjustment factors of 1,2 for light-duty cabinets at chilled operating temperature and 1,1 for light-duty cabinets at frozen operating temperature shall then be applied to the testing results obtained for light-duty cabinets.

  • Professional refrigerated storage cabinets shall be tested:

    • at chilled operating temperature in the case of a combined cabinet containing at least one compartment exclusively intended for chilled operating temperature,

    • at chilled operating temperature in the case of a professional refrigerated storage cabinet which has solely one compartment exclusively intended for chilled operating temperature,

    • at frozen operating temperature in all other cases.