# Commission Regulation (EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process chillers (Text with EEA relevance), Division 1: REQUIREMENTS FOR ENERGY EFFICIENCY

Extent: E+W+S+N.I.

(a)From 1 July 2016, the coefficient of performance (COP) and the seasonal energy performance ratio (SEPR) of condensing units shall not fall below the following values:
Operating temperature
Rated capacity PA
Applicable ratio
Value
Medium
0,2 kW≤ PA ≤ 1 kW
COP
1,20
1 kW< PA ≤ 5 kW
COP
1,40
5 kW < PA ≤ 20 kW
SEPR
2,25
20 kW < PA ≤ 50 kW
SEPR
2,35
Low
0,1 kW≤ PA ≤ 0,4 kW
COP
0,75
0,4 kW< PA ≤ 2 kW
COP
0,85
2 kW < PA ≤ 8kW
SEPR
1,50
8 kW < PA ≤ 20 kW
SEPR
1,60
(b)From 1 July 2018, the coefficient of performance (COP) and the seasonal energy performance ratio (SEPR) of condensing units shall not fall below the following values:
Operating temperature
Rated capacity PA
Applicable ratio
Value
Medium
0,2 kW≤ PA ≤ 1kW
COP
1,40
1 kW< PA ≤ 5 kW
COP
1,60
5 kW < PA ≤ 20 kW
SEPR
2,55
20 kW < PA ≤ 50 kW
SEPR
2,65
Low
0,1 kW≤ PA ≤ 0,4 kW
COP
0,80
0,4 kW< PA ≤ 2 kW
COP
0,95
2 kW < PA ≤ 8 kW
SEPR
1,60
8 kW < PA ≤ 20 kW
SEPR
1,70
(c)For condensing units intended to be charged with a refrigerant fluid with a global warming potential lower than 150, COP and SEPR values can be lower than the values indicated in point 1(a) by a maximum of 15 % and in point 1(b) by a maximum of 10 %
(d)Condensing units capable of operating both at medium and low temperature shall comply with the requirements of each category for which they are declared.

---