# Commission Regulation (EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process chillers (Text with EEA relevance), Division 2: REQUIREMENTS FOR PRODUCT INFORMATION

Extent: E+W+S+N.I.

From 1 July 2016, the following product information on condensing units shall be provided:
(a) the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers, shall contain the following elements:
(i) intended evaporating temperature, expressed in degrees Celsius (medium temperature – 10 °C, low temperature – 35 °C);
(ii) for condensing units with a rated cooling capacity lower than 5kW and 2kW for medium and low temperatures respectively:
the rated COP, at full load and 32 °C ambient temperature, rounded to two decimal places, and rated cooling capacity and power input, expressed in kW and rounded to two decimal places;
the COP value, at full load and 25 °C ambient temperature, rounded to two decimal places, and corresponding cooling capacity and power input, expressed in kW and rounded to two decimal places;
(iii) for condensing units with a rated cooling capacity higher than 5kW and 2kW for medium and low operating temperatures respectively:
the SEPR value, rounded to two decimal places;
the annual electricity consumption, expressed in kWh per year;
the rated cooling capacity, rated power input and rated COP;
the declared cooling capacity and declared power input, expressed in kW and rounded to three decimal places, and the COP value, rounded to two decimal places, at rating points B, C and D;
(iv) for condensing units intended for use at ambient temperature above 35 °C, the COP value, at full load and 43 °C ambient temperature, rounded to two decimal places, and corresponding cooling capacity and power input, expressed in kW and rounded to two decimal places;
(v) the type(s) and name(s) of refrigerant fluid(s) intended to be used with the condensing unit;
(vi) any specific precautions that are to be taken when the condensing unit is maintained;
(vii) any specific precautions that are to be taken to optimise the efficiency of the condensing unit when it is integrated into a refrigerating appliance;
(viii) information relevant for recycling or disposal at end-of-life.
(b) a section of the free access websites of manufacturers for installers and other professionals, their authorised representatives, or importers shall be provided, containing information relevant for:
(i) installation in order to optimise energy efficiency of the appliances;
(ii) non-destructive disassembly for maintenance purposes;
(iii) disassembly and dismantling for disposal at end-of life.
(c) the technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:
(i) the elements specified in point (a);
(ii) where the information relating to a specific model has been obtained by calculation on the basis of design or extrapolation from other combinations, the details of such calculations or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify that model.
Tables 4 and 5 below provide an indicative layout for the requested information
Table 4
Information requirements for condensing units with a rated cooling capacity lower than 5kW and 2kW for medium and low operating temperatures respectively
For condensing units intended to operate at only one evaporating temperature, one of the two columns related to ‘Value’ can be deleted.
Model(s): [information identifying the model(s) to which the information relates]
Refrigerant fluid(s): [information to identify the refrigerant fluid(s) intended to be used with the condensing unit]
Item
Symbol
Value
Unit
Evaporating temperature
t
– 10 °C
– 35 °C
°C
Parameters at full load and ambient temperature 32 °C
Rated cooling capacity
PA
x,xxx
x,xxx
kW
Rated power input
DA
x,xxx
x,xxx
kW
Rated COP
COPA
x,xx
x,xx
Parameters at full load and ambient temperature 25 °C
Cooling capacity
P2
x,xxx
x,xxx
kW
Power input
D2
x,xxx
x,xxx
kW
COP
COP2
x,xx
x,xx
Parameters at full load and ambient temperature 43 °C (where applicable)
Cooling capacity
P3
x,xxx
x,xxx
kW
Power input
D3
x,xxx
x,xxx
kW
COP
COP3
x,xx
x,xx
Other items
Capacity control
fixed/step/variable
Contact details
Name and address of the manufacturer or its authorised representative.
Table 5
Information requirements for condensing units with a rated cooling capacity higher than 5kW and 2kW for medium and low operating temperatures respectively
For condensing units intended to operate at only one evaporating temperature, one of the two columns related to ‘Value’ can be deleted.
Model(s): [information identifying the model(s) to which the information relates]
Refrigerant fluid(s): [information to identify the refrigerant fluid(s) intended to be used with the condensing unit]
Item
Symbol
Value
Unit
Evaporating temperature
t
– 10 °C
– 35 °C
°C
Annual electricity consumption
Q
x
x
kWh/a
Seasonal energy performance ratio
SEPR
x,xx
x,xx
Parameters at full load and ambient temperature 32 °C (point (A)
Rated cooling capacity
PA
x,xx
x,xx
kW
Rated power input
DA
x,xx
x,xx
kW
Rated COP
COPA
x,xx
x,xx
Parameters at part load and ambient temperature 25 °C (point (B)
Declared cooling capacity
PB
x,xx
x,xx
kW
Declared power input
DB
x,xx
x,xx
kW
Declared COP
COPB
x,xx
x,xx
Parameters at part load and ambient temperature 15 °C (point (C)
Declared cooling capacity
Pc
x,xx
x,xx
kW
Declared power input
Dc
x,xx
x,xx
kW
Declared COP
COPC
x,xx
x,xx
Parameters at part load and ambient temperature 5 °C (point (D)
Declared cooling capacity
PD
x,xx
x,xx
kW
Declared power input
DD
x,xx
x,xx
kW
Declared COP
COPD
x,xx
x,xx
Parameters at full load and ambient temperature 43 °C (where applicable)
Cooling capacity
P3
x,xx
x,xx
kW
Power input
D3
x,xx
x,xx
kW
Declared COP
COP3
x,xx
x,xx
Other items
Capacity control
fixed/step/variable
Degradation coefficient for fixed and staged capacity units
Cdc
0,25
Contact details
Name and address of the manufacturer or its authorised representative.

---
Source: https://www.legislation.gov.uk/eur/2015/1095/annex/V/division/2 (the official version)
Page: https://openlegislation.uk/eu-regulation-2015-1095/annex-V/division-2
Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives.