# Commission Regulation (EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process chillers (Text with EEA relevance), Division 1: REQUIREMENTS FOR ENERGY EFFICIENCY

Extent: E+W+S+N.I.

(a) From 1 July 2016, the seasonal energy performance ratio (SEPR) of process chillers shall not fall below the following values:
Heat transfer medium at the condensing side
Operating temperature
Rated cooling capacityPA
Minimum SEPR value
Air
Medium
PA ≤ 300 kW
2,24
PA > 300 kW
2,80
Low
PA ≤ 200 kW
1,48
PA > 200 kW
1,60
Water
Medium
PA ≤ 300 kW
2,86
PA > 300 kW
3,80
Low
PA ≤ 200 kW
1,82
PA > 200 kW
2,10
(b) From 1 July 2018, the seasonal energy performance ratio (SEPR) of process chillers shall not fall below the following values:
Heat transfer medium at the condensing side
Operating temperature
Rated cooling capacityPA
Minimum SEPR value
Air
Medium
PA ≤ 300 kW
2,58
PA > 300 kW
3,22
Low
PA ≤ 200 kW
1,70
PA > 200 kW
1,84
Water
Medium
PA ≤ 300 kW
3,29
PA > 300 kW
4,37
Low
PA ≤ 200 kW
2,09
PA > 200 kW
2,42
(c) For process chillers intended to be charged with a refrigerant fluid with a global warming potential lower than 150, SEPR values can be lower than the values indicated in points 1(a) and (b) by a maximum of 10 %.

---