# Commission Regulation (EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process chillers (Text with EEA relevance), Division 3: At the date of entry into force of this Regulation, the best available technology on the market for process chillers in terms of seasonal energy performance ratio was identified as follows:

Extent: E+W+S+N.I.

Heat transfer medium at the condensing side
Operating temperature
Rated cooling capacityPA
Minimum SEPR value
Air
Medium
PA ≤ 300 kW
3,4
PA > 300 kW
3,7
Low
PA ≤ 200 kW
1,9
PA > 200 kW
1,95
Water
Medium
PA ≤ 300 kW
4,3
PA > 300 kW
4,5
Low
PA ≤ 200 kW
2,3
PA > 200 kW
2,7

---
Source: https://www.legislation.gov.uk/eur/2015/1095/annex/XII/division/3 (the official version)