Annex I Minimum requirements as to the skills and knowledge to be covered by the evaluation bodies

United Kingdom

Original text. Later amendments are not shown.

Commission Regulation (EC) No 1516/2007 of 19 December 2007 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council, standard leakage checking requirements for stationary refrigeration, air conditioning and heat pump equipment containing certain fluorinated greenhouse gases (OJ L 335, 20.12.2007, p. 10).

CATEGORIES
SKILLS AND KNOWLEDGEIIIIIIIV
1Basic thermodynamics
1.01Know the basic ISO standard units as for temperature, pressure, mass, density, energyTT—T
1.02Understand basic theory of refrigeration systems: basic thermodynamics (key terms, parameters and processes such as Superheat, High Side, Heat of Compression, Enthalpy, Refrigeration Effect, Low Side, Sub-cooling), properties and thermodynamic transformations of refrigerants including identification of zeotropic blends and fluid statesTT——
1.03Use relevant tables and diagrams and interpret them in the context of indirect leakage checking (including checking of the good operation of the system): log p/h diagram, saturation tables of a refrigerant, diagram of a single compression refrigeration cycleTT——
1.04Describe the function of the main components in the system (compressor, evaporator, condenser, thermostatic expansion valves) and the thermodynamic transformations of the refrigerantTT——
1.05Know the basic operation of the following components used in a refrigeration system and their role and importance for refrigerant leakage prevention and identification: (a) valves (ball valves, diaphragms, globe valves, relief valves), (b) temperature and pressure controls, (c) sight glasses and moisture indicators, (d) defrost controls, (e) system protectors, (f) measuring devices as manifold thermometer, (g) oil control systems, (h) receivers, (i) liquid and oil separators———
1.06Know about the specific behaviour, physical parameters, solutions, systems, deviances of alternative refrigerants in the refrigeration cycle and components for their useTTTT
2Environmental impact of refrigerants and corresponding environmental regulations
2.01Have a basic knowledge of the F1any part of the United Kingdom and international climate change policy, including the United Nations Framework Convention on Climate ChangeTTTT
2.02Have a basic knowledge of the concept of Global Warming Potential (GWP), the use of fluorinated greenhouse gases and other substances as refrigerants, the impact of the emissions of fluorinated greenhouse gases on the climate (order of magnitude of their GWP) and relevant provisions of Regulation (EU) No 517/2014 and of the relevant implementing actsTTTT
3Checks before putting in operation, after a long period of non-use, after maintenance or repair intervention, or during operation
3.01Carry out a pressure test to check the strength of the systemPP——
3.02Carry out a pressure test to check the tightness of the system
3.03Use a vacuum pump
3.04Evacuate the system to remove air and moisture according to standard practice
3.05Fill in the data in the equipment records and fill in a report about one or more tests and checks carried out during the examinationTT——
4Checks for leakage
4.01Know potential leakage points of refrigeration, air conditioning and heat pump equipmentTT—T
4.02Check equipment records prior to a check for leakage and identify the relevant information on any repeating issues or problem areas to pay special attention toTT—T
4.03Make a visual and manual inspection of the whole system in accordance with Commission Regulation (EC) No 1516/2007f1 PP—P
4.04Carry out a check for leakage of the system using an indirect method in accordance with Regulation (EC) No 1516/2007 and the instruction manual of the systemPP—P
4.05Use portable measuring devices such as manometer sets, thermometers and multi-meters for measuring Volt/Amp/Ohm in the context of indirect methods for leakage checking, and interpret the measured parametersPP—P
4.06Carry out a check for leakage of the system using one of the direct methods referred to in Regulation (EC) No 1516/2007P———
4.07Carry out a check for leakage of the system using one of the direct methods which does not entail breaking into the refrigeration circuit, referred to in Regulation (EC) No 1516/2007—P—P
4.08Use an appropriate electronic leak detection devicePP—P
4.09Fill in the data in the equipment recordsTT—T
5Environment-friendly handling of the system and refrigerant during installation, maintenance, servicing or recovery
5.01Connect and disconnect gauges and lines with minimal emissionsPP——
5.02Empty and fill a refrigerant cylinder in both liquid and vapour statePPP—
5.03Use a recovery set to recover refrigerant and connect and disconnect recovery set with minimal emissionsPPP—
5.04Drain F-gas contaminated oil out of a systemPPP—
5.05Identify refrigerant state (liquid, vapour) and condition (subcooled, saturated or superheated) prior to charging, to ensure correct method and volume of charge. Fill the system with refrigerant (both in the liquid and vapour phase) without loss of refrigerantPP——
5.06Choose the correct type of scales and use them to weigh the refrigerantPPP—
5.07Fill in the equipment records with all relevant information concerning the refrigerant recovered or addedTT——
5.08Know requirements and procedures for handling, reusing, reclaiming, storage and transportation of contaminated refrigerant and oilsTTT—
6Component: installation, putting into operation and maintenance of reciprocating, screw and scroll compressors, single and two-stage
6.01Explain the basic functioning of a compressor (including capacity control and lubricating system) and risks of refrigerant leakage or release associated to itTT——
6.02Install a compressor properly, including control and safety equipment, so that no leak or major release occurs once the system is put into operationPP——
6.03Adjust the safety and control switchesP———
6.04Adjust the suction and discharge valves
6.05Check the oil return system
6.06Start up and shut down a compressor and check the good working conditions of the compressor, including by making measurements during operation of compressorPP——
6.07Write a report about the condition of the compressor which identifies any problems in the functioning of the compressor that could damage the system and eventually lead to refrigerant leakage or release should no action be takenTT——
7Component: installation, putting into operation and maintenance of air cooled and water cooled condensers
7.01Explain the basic functioning of a condenser and risks of leakage associated to itTT——
7.02Adjust a discharge pressure control of the condenserP———
7.03Install a condenser/outdoor unit properly, including control and safety equipment, so that no leak or major release occurs when the system has been put into operationPP——
7.04Adjust the safety and control switchesP———
7.05Check the discharge and liquid lines
7.06Purge non-condensable gases out of the condenser using a refrigeration purging deviceP———
7.07Start up and shut down a condenser and check the good working condition of the condenser including by making measurements during operationPP——
7.08Check the surface of the condenserPP——
7.09Write a report about the condition of the condenser which identifies any problems in the functioning that could damage the system and eventually lead to refrigerant leakage or release should no action be takenTT——
8Component: installation, putting into operation and maintenance of air cooled and water cooled evaporators
8.01Explain the basic functioning of an evaporator (including defrosting system) and risks of leakage associated to itTT——
8.02Adjust an evaporating pressure control of the evaporatorP———
8.03Install an evaporator including control and safety equipment, so that no leak or major release occurs when the system has been put into operationPP——
8.04Adjust the safety and control switchesP———
8.05Check the liquid and suction pipelines in the correct position
8.06Check the hot gas defrost pipeline
8.07Adjust evaporation pressure regulation valve
8.08Start up and shut down an evaporator and check the good working condition of the evaporator, including by making measurement during operationPP——
8.09Check the surface of the evaporatorPP——
8.10Write a report about the condition of the evaporator which identifies any problems in the functioning that could damage the system and eventually lead to refrigerant leakage or release should no action be takenTT——
9Component: installation, putting into operation and servicing of Thermostatic Expansion Valves (TEV) and other components
9.01Explain the basic functioning of different kinds of expansion regulators (thermostatic expansion valves, capillary tubes) and risks of leakage associated to itTT——
9.02Install valves in the correct positionP———
9.03Adjust a mechanical/electronic TEVP———
9.04Adjust mechanical and electronic thermostats
9.05Adjust a pressure-regulated valve
9.06Adjust mechanical and electronic pressure limiters
9.07Check the functioning of an oil separatorP———
9.08Check the condition of a filter dryer
9.09Write a report about the condition of these components which identifies any problems in the functioning that could damage the system and eventually lead to refrigerant leakage or release should no action be takenT———
10Piping: building a leak-tight piping system in a refrigeration installation
10.01Weld, braze and/or solder leak-free joints on metallic tubes, pipes and components that can be used in refrigeration, air conditioning or heat pump systemsPP——
10.02Make/check pipe and component supportsPP——
11Information on relevant technologies to replace or to reduce the use of fluorinated greenhouse gases and their safe handling
11.01Know the relevant alternative technologies to replace or to reduce the use of fluorinated greenhouse gases and about their safe handlingTTTT
11.02Know relevant system designs to reduce the charge size of fluorinated greenhouse gases and to increase energy efficiencyTT——
11.03Know relevant safety regulations and standards for the use, storage and transportation of flammable or toxic refrigerants or refrigerants requiring higher operating pressureTT——
11.04Understand the respective advantages and disadvantages, notably in relation to energy efficiency, of alternative refrigerants according to the intended application and to the climate conditions of the different regionsTT——
  1. 1The examination for each of the Categories referred to in Article 3(2) shall comprise the following:
  2. 2Division 2
  3. 3Division 3
  4. 4Division 4

Annotations

Textual amendments

F1

Words in Annex 1 Table substituted (31.12.2020) by The Ozone-Depleting Substances and Fluorinated Greenhouse Gases (Amendment etc.) (EU Exit) Regulations 2019 (S.I. 2019/583), regs. 1, 69(8); 2020 c. 1, Sch. 5 para. 1(1)

Footnotes

f1

Commission Regulation (EC) No 1516/2007 of 19 December 2007 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council, standard leakage checking requirements for stationary refrigeration, air conditioning and heat pump equipment containing certain fluorinated greenhouse gases (OJ L 335, 20.12.2007, p. 10).