Division Correction factors for avoided grid losses for the (referred to in Article 2(2))
United Kingdom
| Connection voltage level | Correction factor (Off-site) | Correction factor (On-site) |
|---|---|---|
| ≥ 345 kV | 1 | 0,976 |
| ≥ 200 - < 345 kV | 0,972 | 0,963 |
| ≥ 100 - < 200 kV | 0,963 | 0,951 |
| ≥ 50 - < 100 kV | 0,952 | 0,936 |
| ≥ 12 - < 50 kV | 0,935 | 0,914 |
| ≥ 0,45 - < 12kV | 0,918 | 0,891 |
| < 0,45 kV | 0,888 | 0,851 |
After the grid loss correction the resulting efficiency reference value for the separate production of electricity in this cogeneration unit would be (based on the weighted mean of the factors in this Annex):
Ref Εη = 52,5 % × (0,851 × 85 % + 0,888 × 15 %) = 45,0 %