# Commission Regulation (EU) 2016/1447 of 26 August 2016 establishing a network code on requirements for grid connection of high voltage direct current systems and direct current-connected power park modules (Text with EEA relevance), Annex IV: Requirements for U-Q/Pmax-profile referred to in Article 20

Extent: E+W+S+N.I.

Figure 5: The diagram represents boundaries of a U-Q/Pmax-profile with U being the voltage at the connection points expressed by the ratio of its actual value to its reference 1 pu value in per unit, and Q/Pmax the ratio of the reactive power to the maximum HVDC active power transmission capacity. The position, size and shape of the inner envelope are indicative and shapes other than rectangular may be used within the inner envelope. For profile shapes other than rectangular, the voltage range represents the highest and lowest voltage points in this shape. Such a profile would not give rise to the full reactive power range being available across the range of steady-state voltages.
Synchronous Area
Maximum range of Q/Pmax
Maximum range of steady-state Voltage level in PU
. . .
. . .
. . .
. . .
. . .
. . .
Great Britain
0.95
0.225
. . .
. . .
. . .
. . .
. . .
. . .
Table 6: Parameters for the Inner Envelope in the Figure.

---