# Commission Regulation (EU) 2016/2281 of 30 November 2016 implementing Directive 2009/125/EC of the European Parliament and of the Council establishing a framework for the setting of ecodesign requirements for energy-related products, with regard to ecodesign requirements for air heating products, cooling products, high temperature process chillers and fan coil units (Text with EEA relevance), Division 3: Seasonal energy performance ratio of high temperature process chillers:

Extent: E+W+S+N.I.

(a) From 1 January 2018, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 5:
Table 5
First tier seasonal energy performance ratio of high temperature process chillers
To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.
Heat transfer medium at the condensing side
Rated refrigeration capacity
Minimum SEPR value
Air
PA < 400 kW
4,5
PA ≥ 400 kW
5,0
Water
PA < 400 kW
6,5
400 kW ≤ PA < 1 500 kW
7,5
PA ≥ 1 500 kW
8,0
(b) From 1 January 2021, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 6:
Table 6
Second tier seasonal energy performance ratio of high temperature process chillers
To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.
Heat transfer medium at the condensing side
Rated refrigeration capacity
Minimum SEPR value
Air
PA < 400 kW
5,0
PA ≥ 400 kW
5,5
Water
PA < 400 kW
7,0
400 kW ≤ PA < 1 500 kW
8,0
PA ≥ 1 500 kW
8,5

---