# Commission Regulation (EU) 2016/2281 of 30 November 2016 implementing Directive 2009/125/EC of the European Parliament and of the Council establishing a framework for the setting of ecodesign requirements for energy-related products, with regard to ecodesign requirements for air heating products, cooling products, high temperature process chillers and fan coil units (Text with EEA relevance), Annex III: Measurement and calculation

Extent: E+W+S+N.I.

For establishing the values of rated and declared cooling capacity, power input, energy efficiency ratio and the seasonal energy performance ratio, measurements shall be done using the following conditions:
(a)the reference ambient temperature at the outdoor side heat exchanger shall be 35 °C for air-cooled high temperature process chillers and 30 °C water inlet temperature to the condenser (rating point with 35 °C outdoor air temperature) for water-cooled high temperature process chillers
(b)the outlet temperature of the liquid at the indoor side heat exchanger shall be 7 °C dry bulb temperature;
(c)the variations of the ambient temperature throughout the year, representative of average climate conditions in the European Union, and the corresponding number of hours when these temperatures occur, shall be as set out in Table 28;
(d)the effect of the degradation of energy efficiency caused by cycling depending on the type of capacity control of the high temperature process chiller shall be measured or a default value shall be used.
Table 16
Standard rating conditions for air-to-air heat pumps and air conditioners
The wet bulb temperature condition is not required when testing units which do not evaporate condensate.
Outdoor side heat exchanger
Indoor side heat exchanger
inlet dry bulb temperature °C
inlet wet bulb temperature °C
inlet dry bulb temperature °C
inlet wet bulb temperature °C
Heating mode (for heat pumps)
Outside air/recycled air
7
6
20
15 max
Exhaust air/outdoor air
20
12
7
6
Cooling mode (for air conditioners)
Outside air/recycled air
35
24
27
19
Exhaust air/recycled air
27
19
27
19
Exhaust air/outdoor air
27
19
35
24
Table 17
Standard rating conditions for water/brine-to-water comfort chillers
Outdoor side heat exchanger
Indoor side heat exchanger
inlet temperature °C
outlet temperature °C
inlet temperature °C
outlet temperature °C
Cooling mode
water-to-water (for low temperature heating applications) from cooling tower
30
35
12
7
water-to-water (for medium temperature heating applications) from cooling tower
30
35
23
18
Table 18
Standard rating conditions air-to-water comfort chillers
Outdoor side heat exchanger
Indoor side heat exchanger
inlet temperature °C
outlet temperature °C
inlet temperature °C
outlet temperature °C
Cooling mode
air-to-water (for low temperature applications)
35
—
12
7
air-to-water (for medium temperature applications)
35
—
23
18
Table 19
Standard rating conditions for water/brine-to-air heat pumps and air conditioners
For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in cooling mode is used.
Outdoor side heat exchanger
Indoor side heat exchanger
inlet temperature °C
outlet temperature °C
inlet dry bulb temperature °C
inlet wet bulb temperature °C
Heating mode (for heat pumps)
water
10
7
20
15 max
brine
0
– 3
20
15 max
water loop
20
17
20
15 max
Cooling mode (for air conditioners)
cooling tower
30
35
27
19
ground coupled (water or brine)
10
15
27
19
Table 20
Reference ambient temperatures for high temperature process chillers
Test point
Part load ratio of high temperature process chillers
Part load ratio (%)
Outdoor side heat exchanger (°C)
Indoor side heat exchanger
Evaporator inlet/outlet water temperatures (°C)
Fixed outlet
A
80 % + 20 % × (TA -TD )/(TA -TD )
100
Inlet air temperature
35
12/7
Inlet/outlet water temperatures
30/35
Table 21
Part load conditions for air conditioners, comfort chillers and heat pumps
Outlet temperatures dependent on water flow rate as determined at standard rating conditions (100 % part load ratio when cooling, 88 % when heating)
Rating point
Outdoor temperature
Part load ratio
Outdoor side heat exchanger
Indoor side heat exchanger
Air-to-air air conditioners
Tj (°C)
Outdoor air dry bulb temperatures (°C)
Indoor air dry bulb (wet bulb) temperatures (°C)
A
35
100 %
35
27 (19)
B
30
74 %
30
27 (19)
C
25
47 %
25
27 (19)
D
20
21 %
20
27 (19)
Water-to-air air conditioners
Rating point
Tj (°C)
Part load ratio
Cooling tower or water loop application inlet/outlet temperatures (°C)
Ground coupled application (water or brine) inlet/outlet temperatures (°C)
Indoor air dry bulb (wet bulb) temperatures (°C)
A
35
100 %
30/35
10/15
27 (19)
B
30
74 %
26/
10/
27 (19)
C
25
47 %
22/
10/
27 (19)
D
20
21 %
18/
10/
27 (19)
Air-to-water comfort chillers
Rating point
Tj (°C)
Part load ratio
Outdoor air dry bulb temperatures (°C)
Fan coil application inlet/outlet water temperatures (°C)
Cooling floor application inlet/outlet water temperatures (°C)
Fixed outlet
Variable outlet
A
35
100 %
35
12/7
12/7
23/18
B
30
74 %
30
/7
/8,5
/18
C
25
47 %
25
/7
/10
/18
D
20
21 %
20
/7
/11,5
/18
Water-to-water comfort chillers
Rating point
Tj (°C)
Part load ratio
Cooling tower or water loop application inlet/outlet temperatures (°C)
Ground coupled application (water or brine) inlet/outlet temperatures (°C)
Fan coil application inlet/outlet water temperatures (°C)
Cooling floor application inlet/outlet water temperatures (°C)
Fixed outlet
Variable outlet
A
35
100 %
30/35
10/15
12/7
12/7
23/18
B
30
74 %
26/
10/
/7
/8,5
/18
C
25
47 %
22/
10/
/7
/10
/18
D
20
21 %
18/
10/
/7
/11,5
/18
Air-to-air heat pumps
Rating point
Tj (°C)
Part load ratio
Outdoor air dry bulb (wet bulb) temperatures (°C)
Indoor air dry bulb temperature (°C)
A
– 7
88 %
– 7(– 8)
20
B
+ 2
54 %
+ 2(+ 1)
20
C
+ 7
35 %
+ 7(+ 6)
20
D
+ 12
15 %
+ 12(+ 11)
20
E
Tol
depends on Tol
Tj = Tol
20
F
Tbiv
depends on Tbiv
Tj = Tbiv
20
Water/brine-to-air heat pumps
Rating point
Tj (°C)
Part load ratio
Ground Water
Brine
Indoor air dry bulb temperature (°C)
Inlet/outlet temperatures (°C)
Inlet/outlet temperatures (°C)
A
– 7
88 %
10/
0/
20
B
+ 2
54 %
10/
0/
20
C
+ 7
35 %
10/
0/
20
D
+ 12
15 %
10/
0/
20
E
Tol
depends on Tol
10/
0/
20
F
Tbiv
depends on Tbiv
10/
0/
20
Table 22
Part load conditions for SEPR calculation for air-cooled high temperature process chillers
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.
Rating point
Part load ratio of high temperature process chillers
Part load ratio (%)
Outdoor side heat exchanger
Indoor side heat exchanger
Inlet air temperature (°C)
Evaporator inlet/outlet water temperatures (°C)
Fixed outlet
A
80 % + 20 % × (TA -TD )/(TA -TD )
100
35
12/7
B
80 % + 20 % × (TB -TD )/(TA -TD )
93
25
/7
C
80 % + 20 % × (TC -TD )/(TA -TD )
87
15
/7
D
80 % + 20 % × (TD -TD )/(TA -TD )
80
5
/7
Table 23
Part load conditions for SEPR calculation for water-cooled high temperature process chillers
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.
Rating point
Part load ratio of high temperature process chillers
Part load ratio (%)
Water-cooled condenser
Indoor side heat exchanger
Inlet/outlet water temperatures (°C)
Outdoor air temperature (°C)
Evaporator Inlet/outlet water temperatures (°C)
Fixed outlet
A
80 % + 20 % × (TA -TD )/(TA -TD )
100
30/35
35
12/7
B
80 % + 20 % × (T B-T D)/(T A-T D)
93
23/
25
/7
C
80 % + 20 % × (T C-T D)/(T A-T D)
87
16/
15
/7
D
80 % + 20 % × (TD-TD)/(TA-TD)
80
9/
5
/7
Table 24
Reference design conditions for comfort chillers, air conditioners and heat pumps
Function
Season
Reference design temperature dry bulb (wet bulb)
Tdesign,c
Cooling
Average
35 (24) °C
Reference design temperature
Bivalent temperature maximum
Operation limit temperature maximum
Tdesign,h
Tbiv
Tol
Heating
Average
– 10 (– 11) °C
+ 2 °C
– 7 °C
Warmer
2 (– 1) °C
7 °C
2 °C
Colder
– 22 (– 23) °C
– 7 °C
– 15 °C
Table 25
Standard rating conditions for fan coil units
Cooling test
Heating test
Sound power test
Air temperature
27 °C (dry bulb)
19 °C (wet bulb)
Air temperature
20 °C (dry bulb)
At ambient conditions without water flow
Inlet water temperature
7 °C
Inlet water temperature
45 °C for 2-pipe units
65 °C for 4-pipe units
Water temperature rise
5 °C
Water temperature decrease
5 °C for 2-pipe units
10 °C for 4-pipe units
Table 26
European heating seasons for heat pumps
binj
Tj (°C)
Hj (h/annum)
Warmer
Average
Colder
1 to 8
– 30 to – 23
0
0
0
9
– 22
0
0
1
10
– 21
0
0
6
11
– 20
0
0
13
12
– 19
0
0
17
13
– 18
0
0
19
14
– 17
0
0
26
15
– 16
0
0
39
16
– 15
0
0
41
17
– 14
0
0
35
18
– 13
0
0
52
19
– 12
0
0
37
20
– 11
0
0
41
21
– 10
0
1
43
22
– 9
0
25
54
23
– 8
0
23
90
24
– 7
0
24
125
25
– 6
0
27
169
26
– 5
0
68
195
27
– 4
0
91
278
28
– 3
0
89
306
29
– 2
0
165
454
30
– 1
0
173
385
31
0
0
240
490
32
1
0
280
533
33
2
3
320
380
34
3
22
357
228
35
4
63
356
261
36
5
63
303
279
37
6
175
330
229
38
7
162
326
269
39
8
259
348
233
40
9
360
335
230
41
10
428
315
243
42
11
430
215
191
43
12
503
169
146
44
13
444
151
150
45
14
384
105
97
46
15
294
74
61
Total hours:
3 590
4 910
6 446
Table 27
European cooling season for comfort chillers and air conditioners
Bins
Outdoor temperature (dry bulb)
‘Average cooling season’
EER calculation
bin hours
j
Tj
hj
#
°C
h/annum
1
17
205
EER(D)
2
18
227
EER(D)
3
19
225
EER(D)
4
20
225
D — Measured value
5
21
216
Linear interpolation
6
22
215
Linear interpolation
7
23
218
Linear interpolation
8
24
197
Linear interpolation
9
25
178
C — Measured value
10
26
158
Linear interpolation
11
27
137
Linear interpolation
12
28
109
Linear interpolation
13
29
88
Linear interpolation
14
30
63
B — Measured value
15
31
39
Linear interpolation
16
32
31
Linear interpolation
17
33
24
Linear interpolation
18
34
17
Linear interpolation
19
35
13
A — Measured value
20
36
9
EER(A)
21
37
4
EER(A)
22
38
3
EER(A)
23
39
1
EER(A)
24
40
0
EER(A)
Table 28
European reference refrigeration season for high temperature process chillers
binj
Tj (°C)
Hj (h/annum)
1
– 19
0,08
2
– 18
0,41
3
– 17
0,65
4
– 16
1,05
5
– 15
1,74
6
– 14
2,98
7
– 13
3,79
8
– 12
5,69
9
– 11
8,94
10
– 10
11,81
11
– 9
17,29
12
– 8
20,02
13
– 7
28,73
14
– 6
39,71
15
– 5
56,61
16
– 4
76,36
17
– 3
106,07
18
– 2
153,22
19
– 1
203,41
20
0
247,98
21
1
282,01
22
2
275,91
23
3
300,61
24
4
310,77
25
5
336,48
26
6
350,48
27
7
363,49
28
8
368,91
29
9
371,63
30
10
377,32
31
11
376,53
32
12
386,42
33
13
389,84
34
14
384,45
35
15
370,45
36
16
344,96
37
17
328,02
38
18
305,36
39
19
261,87
40
20
223,90
41
21
196,31
42
22
163,04
43
23
141,78
44
24
121,93
45
25
104,46
46
26
85,77
47
27
71,54
48
28
56,57
49
29
43,35
50
30
31,02
51
31
20,21
52
32
11,85
53
33
8,17
54
34
3,83
55
35
2,09
56
36
1,21
57
37
0,52
58
38
0,40
Table 29
Operational hours per functional mode for comfort chillers, air conditioners and heat pumps
Season
Operational hours
On-mode
Thermostat Off mode
Standby mode
Off mode
Crankcase heater mode
HCE (cooling); HHE (heating)
HTO
HSB
HOFF
HCK
Cooling (to calculate SEER)
Average
600
659
1 377
0
2 036
Colder
300
436
828
0
1 264
Warmer
900
767
1 647
0
2 414
Heating only (to calculate SCOP)
Average
1 400
179
0
3 672
3 851
Colder
2 100
131
0
2 189
2 320
Warmer
1 400
755
0
4 345
5 100
Heating, if reversible (to calculate SCOP)
Average
1 400
179
0
0
179
Colder
2 100
131
0
0
131
Warmer
1 400
755
0
0
755

---