# Commission Delegated Regulation (EU) 2016/364 of 1 July 2015 on the classification of the reaction to fire performance of construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council (Text with EEA relevance), Annex: Classes of reaction to fire performance

Extent: E+W+S+N.I.

Table 1
Classes of reaction to fire performance for construction products excluding floorings, linear pipe thermal insulation products, and electric cables
For homogeneous products and substantial components of non-homogeneous products.
For any external non-substantial component of non-homogeneous products.
(2a) Alternatively, any external non-substantial component having a PCS ≤ 2,0 MJm– 2, provided that the product satisfies the following criteria of EN 13823(SBI): FIGRA ≤ 20 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 4,0 MJ; and s1; and d0.
For any internal non-substantial component of non-homogeneous products.
For the product as a whole.
s1 = SMOGRA ≤ 30m2s– 2 and TSP600s ≤ 50m2; s2 = SMOGRA ≤ 180m2s– 2 and TSP600s ≤ 200m2; s3 = not s1 or s2.
d0 = No flaming droplets/particles in EN 13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN 13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
No ignition of the paper = no additional classification; Ignition of the paper = d2 classification.
Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
Class
Test method(s)
Classification criteria
Additional classification
A1
EN ISO 1182;
and
ΔΤ ≤ 30 °C; and
Δm ≤ 50 %; and
tf = 0 (i.e. no sustained flaming)
EN ISO 1716
PCS ≤ 2,0 MJkg– 1 ; and
PCS ≤ 2,0 MJkg– 1 ; and
PCS ≤ 1,4 MJm– 2 ; and
PCS ≤ 2,0 MJkg– 1
A2
EN ISO 1182;
or
ΔΤ ≤ 50 °C; and
Δm ≤ 50 %; and
tf ≤ 20 s
EN ISO 1716;
and
PCS ≤ 3,0 MJkg– 1 ; and
PCS ≤ 4,0 MJm– 2 ; and
PCS ≤ 4,0 MJm– 2 ; and
PCS ≤ 3,0 MJkg– 1
EN 13823 (SBI)
FIGRA ≤ 120 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
B
EN 13823 (SBI);
and
FIGRA ≤ 120 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
C
EN 13823 (SBI);
and
FIGRA ≤ 250 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 15 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
D
EN 13823 (SBI);
and
FIGRA ≤ 750 Ws– 1
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
E
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
Flaming droplets/particles
F
EN ISO 11925-2:
Exposure = 15 s
Fs > 150 mm within 20 s
Table 2
Classes of reaction to fire performance for floorings
For homogeneous products and substantial components of non-homogeneous products.
For any external non-substantial component of non-homogeneous products.
For any internal non-substantial component of non-homogeneous products.
For the product as a whole.
Test duration = 30 minutes.
Critical flux is defined as the radiant flux at which the flame extinguishes or the radiant flux after a test period of 30 minutes, whichever is the lower (i.e. the flux corresponding with the furthest extent of spread of flame).
s1 = Smoke ≤ 750 %.min; s2 = not s1.
Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
Class
Test method(s)
Classification criteria
Additional classification
A1FL
EN ISO 1182;
and
ΔΤ ≤ 30 °C; and
Δm ≤ 50 %; and
tf = 0 (i.e. no sustained flaming)
EN ISO 1716
PCS ≤ 2,0 MJkg– 1 ; and
PCS ≤ 2,0 MJkg– 1 ; and
PCS ≤ 1,4 MJm– 2 ; and
PCS ≤ 2,0 MJkg– 1
A2FL
EN ISO 1182;
or
ΔΤ ≤ 50 °C; and
Δm ≤ 50 %; and
tf ≤ 20 s
EN ISO 1716;
and
PCS ≤ 3,0 MJkg– 1 ; and
PCS ≤ 4,0 MJm– 2 ; and
PCS ≤ 4,0 MJm– 2 ; and
PCS ≤ 3,0 MJkg– 1
EN ISO 9239-1
Critical flux ≥ 8,0 kWm– 2
Smoke production
BFL
EN ISO 9239-1
and
Critical flux ≥ 8,0 kWm– 2
Smoke production
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
CFL
EN ISO 9239-1
and
Critical flux ≥ 4,5 kWm– 2
Smoke production
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
DFL
EN ISO 9239-1
and
Critical flux ≥ 3,0 kWm– 2
Smoke production
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
EFL
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
FFL
EN ISO 11925-2:
Exposure = 15 s
Fs > 150 mm within 20 s
Table 3
Classes of reaction to fire performance for linear pipe insulation products
For homogeneous products and substantial components of non-homogeneous products.
For any external non-substantial component of non-homogeneous products.
For any internal non-substantial component of non-homogeneous products.
For the product as a whole.
s1 = SMOGRA ≤ 105 m2s– 2 and TSP600s ≤ 250 m2; s2 = SMOGRA ≤ 580 m2s– 2 and TSP600s ≤ 1 600 m2; s3 = not s1 or s2.
d0 = No flaming droplets/particles in EN13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
No ignition of the paper = no additional classification; Ignition of the paper = d2 classification.
Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
Class
Test method(s)
Classification criteria
Additional classification
A1L
EN ISO 1182;
and
ΔT ≤ 30 °C; and
Δm ≤ 50 %; and
tf = 0 (i.e. no sustained flaming)
EN ISO 1716
PCS ≤ 2,0 MJkg– 1 ; and
PCS ≤ 2,0 MJkg– 1 ; and
PCS ≤ 1,4 MJm– 2 ; and
PCS ≤ 2,0 MJkg– 1
A2L
EN ISO 1182;
or
ΔT ≤ 50 °C; and
Δm ≤ 50 %; and tf ≤ 20 s
EN ISO 1716;
and
PCS ≤ 3,0 MJkg– 1 ; and
PCS ≤ 4,0 MJm– 2 ; and
PCS ≤ 4,0 MJm– 2 ; and
PCS ≤ 3,0 MJkg– 1
EN 13823 (SBI)
FIGRA ≤ 270 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
BL
EN 13823 (SBI);
and
FIGRA ≤ 270 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
CL
EN 13823 (SBI);
and
FIGRA ≤ 460 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 15 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
DL
EN 13823 (SBI);
and
FIGRA ≤ 2 100 Ws– 1
THR600s ≤ 100 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
EL
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
Flaming droplets/particles
FL
EN ISO 11925-2:
Exposure = 15 s
Fs > 150mm within 20 s
Table 4
Classes of reaction to fire performance for electric cables
For the product as a whole, excluding metallic materials, and for any external component (i.e. sheath) of the product.
s1 = TSP1200 ≤ 50 m2 and Peak SPR ≤ 0,25 m2/s
s1a = s1 and transmittance in accordance with EN 61034-2 ≥ 80 %
s1b = s1 and transmittance in accordance with EN 61034-2 ≥ 60 % < 80 %
s2 = TSP1200 ≤ 400 m2 and Peak SPR ≤ 1,5 m2/s
s3 = not s1 or s2
d0 = No flaming droplets/particles within 1 200 s; d1 = No flaming droplets/particles persisting longer than 10 s within 1 200 s; d2 = not d0 or d1.
EN 60754-2: a1 = conductivity < 2,5 μS/mm and pH > 4,3; a2 = conductivity < 10 μS/mm and pH > 4,3; a3 = not a1 or a2.
The smoke class declared for class B1ca cables must originate from the EN 50399 test (30 kW flame source).
The smoke class declared for class B2ca, Cca, Dca cables must originate from the EN 50399 test (20,5 kW flame source).
Class
Test method(s)
Classification criteria
Additional classification
Aca
EN ISO 1716
PCS ≤ 2,0 MJ/kg
B1ca
EN 50399 (30 kW flame source)
and
FS ≤ 1,75 m and
THR1200s ≤ 10 MJ and
Peak HRR ≤ 20 kW and
FIGRA ≤ 120 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2
H ≤ 425 mm
B2ca
EN 50399 (20,5 kW flame source)
and
FS ≤ 1,5 m; and
THR1200s ≤ 15 MJ; and
Peak HRR ≤ 30 kW; and
FIGRA ≤ 150 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2
H ≤ 425 mm
Cca
EN 50399 (20,5 kW flame source)
and
FS ≤ 2,0 m; and
THR1200s ≤ 30 MJ; and
Peak HRR ≤ 60 kW; and
FIGRA ≤ 300 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2
H ≤ 425 mm
Dca
EN 50399 (20,5 kW flame source)
and
THR1200s ≤ 70 MJ; and
Peak HRR ≤ 400 kW; and
FIGRA ≤ 1 300 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2
H ≤ 425 mm
Eca
EN 60332-1-2
H ≤ 425 mm
Fca
EN 60332-1-2
H > 425 mm

---