Division 1.3 For the purposes of Table 4 the following symbols and test parameters apply:
United Kingdom
heat release rate averaged by a 30-s sliding average;
smoke production rate averaged by a 60-s sliding average;
maximum of HRRsm30 between test start and end of test, excluded contribution from ignition source;
maximum of SPRsm60 between test start and end of test;
total heat release (HRRsm30) from test start until end of test, excluded contribution from ignition source;
total smoke production (HRRsm60) from test start until end of test;
fire growth rate index defined as the highest value of the quotient between HRRsm30 excluding the contribution of ignition source and time. Threshold values HRRsm30 = 3 kW and THR = 0,4 MJ;
flame spread (damaged length);
flame spread.
Notes on Annex
Footnotes
- f1
-
For homogeneous products and substantial components of non-homogeneous products.
- f2
-
For any external non-substantial component of non-homogeneous products.
- f3
-
- (2a)
Alternatively, any external non-substantial component having a PCS ≤ 2,0 MJm– 2, provided that the product satisfies the following criteria of EN 13823(SBI): FIGRA ≤ 20 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 4,0 MJ; and s1; and d0.
- (2a)
- f4
-
For any internal non-substantial component of non-homogeneous products.
- f5
-
For the product as a whole.
- f6
-
s1 = SMOGRA ≤ 30m2s– 2 and TSP600s ≤ 50m2; s2 = SMOGRA ≤ 180m2s– 2 and TSP600s ≤ 200m2; s3 = not s1 or s2.
- f7
-
d0 = No flaming droplets/particles in EN 13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN 13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
- f8
-
Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
- f9
-
No ignition of the paper = no additional classification; Ignition of the paper = d2 classification.
- f10
-
For homogeneous products and substantial components of non-homogeneous products.
- f11
-
For any external non-substantial component of non-homogeneous products.
- f12
-
For any internal non-substantial component of non-homogeneous products.
- f13
-
For the product as a whole.
- f14
-
Test duration = 30 minutes.
- f15
-
Critical flux is defined as the radiant flux at which the flame extinguishes or the radiant flux after a test period of 30 minutes, whichever is the lower (i.e. the flux corresponding with the furthest extent of spread of flame).
- f16
-
s1 = Smoke ≤ 750 %.min; s2 = not s1.
- f17
-
Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
- f18
-
For homogeneous products and substantial components of non-homogeneous products.
- f19
-
For any external non-substantial component of non-homogeneous products.
- f20
-
For any internal non-substantial component of non-homogeneous products.
- f21
-
For the product as a whole.
- f22
-
s1 = SMOGRA ≤ 105 m2s– 2 and TSP600s ≤ 250 m2; s2 = SMOGRA ≤ 580 m2s– 2 and TSP600s ≤ 1 600 m2; s3 = not s1 or s2.
- f23
-
d0 = No flaming droplets/particles in EN13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
- f24
-
Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
- f25
-
No ignition of the paper = no additional classification; Ignition of the paper = d2 classification.
- f26
-
For the product as a whole, excluding metallic materials, and for any external component (i.e. sheath) of the product.
- f27
-
s1 = TSP1200 ≤ 50 m2 and Peak SPR ≤ 0,25 m2/s
s1a = s1 and transmittance in accordance with EN 61034-2 ≥ 80 %
s1b = s1 and transmittance in accordance with EN 61034-2 ≥ 60 % < 80 %
s2 = TSP1200 ≤ 400 m2 and Peak SPR ≤ 1,5 m2/s
s3 = not s1 or s2
- f28
-
The smoke class declared for class B1ca cables must originate from the EN 50399 test (30 kW flame source).
- f29
-
d0 = No flaming droplets/particles within 1 200 s; d1 = No flaming droplets/particles persisting longer than 10 s within 1 200 s; d2 = not d0 or d1.
- f30
-
EN 60754-2: a1 = conductivity < 2,5 μS/mm and pH > 4,3; a2 = conductivity < 10 μS/mm and pH > 4,3; a3 = not a1 or a2.
- f31
-
The smoke class declared for class B2ca, Cca, Dca cables must originate from the EN 50399 test (20,5 kW flame source).