Division 3.3.2.4 Dew point determination from relative humidity and dry bulb temperature

United Kingdom

Original text. Later amendments are not shown.

If humidity is measured as a relative humidity, RH %, the dew point, T dew, shall be determined from RH % and dry bulb temperature by means of equation (7-81):

T dew = 2,0798233 × 10 2 − 2,0156028 × 10 1 × ln p H2O + 4,6778925 × 10 – 1 × ln p H2O 2 − 9,2288067 × 10 – 6 × ln p H2O 3 1 − 1,3319669 × 10 – 1 × ln p H2O + 5,6577518 × 10 – 3 × ln p 2 H2O − 7,517286510 × 10 – 5 ln p 3 H2O

(7-81)

Where

p H2O
  • water vapor pressure scaled to the relative humidity at the location of relative humidity measurement, T sat = T amb

  • T dew
  • dew point as determined from relative humidity and dry bulb temperature measurements