Annex Classes of performance in relation to air permeability for roof lights of plastics and glass and roof hatches
United Kingdom
| In case of class A, in addition to declaring the class, the worst measurement of all pressure steps shall also be declared using the following template: Class A (internal pressure (100Pa), assessed leakage rate). | ||
| Note: The boundaries of the classes used in this Table may be derived from the following formula: Where: Qis the leakage rate in m3 per hour, per linear m rooflight perimeter during a test under internal pressure is the internal pressure during a test (in Pa) is the leakage rate in m3 per hour, per linear m rooflight perimeter at an internal pressure of 100 Pa | ||
| Class | Lower limit value of Internal Pressure(4 Pa) | Higher limit value of Internal Pressure(100 Pa) |
|---|---|---|
| Air permeability(in m3/(h.m)) | ||
| Af1 | < 1,4 | < 12 |
| B | ≥ 1,4 | ≥ 12 |
| C | ≥ 6 | ≥ 50 |
Annotations
Footnotes
- f1
-
In case of class A, in addition to declaring the class, the worst measurement of all pressure steps shall also be declared using the following template: Class A (internal pressure (100Pa), assessed leakage rate).