From 1 March 2020, the following product information on servers and online data storage products shall be provided in the technical documentation for the purposes of conformity assessment pursuant to Article 4:

  1. (a)

    Information listed in points 3.1 and 3.3, in the case of servers

  2. (b)

    Information listed in points 3.2 and 3.3, in the case of data storage products

Table 6

Operating condition classes

Dry bulb temp °CHumidity range, non-condensing
Operating condition classAllowable rangeRecommended rangeAllowable rangeRecommended rangeMax dew point (°C)Maximum rate of change (°C/hr)
A115- 3218-27

– 12 °C Dew Point (DP) and 8 % relative humidity (RH) to

17 °C DP and 80 % RH

– 9 °C DP to

15 °C DP and 60 % RH

175/20
A210-3518-27

– 12 °C DP and 8 % RH to

21 °C DP and 80 % RH

Same as A1215/20
A35-4018-27

– 12 °C DP and 8 % RH to

24 °C DP and 85 % RH

Same as A1245/20
A45-4518-27

– 12 °C DP and 8 % RH to

24 °C DP and 90 % RH

Same as A1245/20