Division 4.4.2 Use-specific risk mitigation measures
United Kingdom
Apply the product only in a sufficiently ventilated room. The minimum air change rates required are
-
8/h in laboratories,
-
60/h in pharmaceutical and cosmetics manufacturing facilities,
-
150/h in cleanrooms.