Article 101 Requirements for vessels of 60 metres in length and over

Original text. Later amendments are not shown.

(1)

In every vessel of 60 metres in length and over to which these Rules apply fire appliances shall be provided whereby at least two jets of water can reach any part of the vessel normally accessible to the crew while the vessel is being navigated, and any store room and any part of any hold space when empty.

(2)

In every such vessel at least two fire pumps operated by power shall be provided. Each pump shall be capable of delivering at least one jet simultaneously from each of any two fire hydrants, hoses and nozzles provided in the vessel and shall comply with the requirements of Rule 107 of these Rules.

(3)

In every such vessel—

(a)

where a fire in any one compartment could put all the fire pumps out of action there shall be provided, in a position outside the machinery spaces, an independently driven power operated emergency fire pump and its source of power and sea connection;

(b)

the emergency fire pump shall be capable of producing at least two jets of water from any of the fire hydrants and hoses through nozzles which shall comply with Rule 109(3)(a) of these Rules while simultaneously maintaining pressure of at least 2 kilogrammes force per square centimetre at any hydrant in the vessel.

(4)

In every such vessel—

(a)

a fire main, water service pipes and hydrants shall be provided which shall comply with the requirements of Rule 108 of these Rules;

(b)

at least one fire hose for each 30 metres length of vessel but in no case less than five hoses in addition to any fire hoses provided in the machinery spaces, shall be provided and these hoses shall have a total length of at least 60 per cent of the length of the vessel. In addition to these hoses there shall be provided one spare fire hose;

(c)

where oil-fired boilers or internal combustion type propelling machinery is installed there shall be provided in each space containing such boilers or machinery at least two fire hydrants, one on the port side and one on the starboard side and in addition where there is access to the machinery space by way of a shaft tunnel a fire hydrant shall be provided in the tunnel at the end adjacent to that space. A fire hose and spray nozzle shall be provided at every such fire hydrant.

(5)

In every such vessel a sufficient number of portable fire extinguishers shall be provided to ensure that at least one such extinguisher will be readily available for use in any part of the accommodation or service spaces. Not less than six extinguishers shall be provided of which one extinguisher suitable for extinguishing oil fires shall be provided adjacent to any oil fired central heating appliance which may be fitted. The extinguishing medium provided in any extinguisher placed in an area of fire risk shall be suitable for the type of fire risk involved.

(6)

In every such vessel at least one of the following fixed fire extinguishing installations shall be provided for the protection of any space containing any oil-fired boiler, oil fuel settling tank or oil fuel unit:—

(a)

a pressure water spraying system complying with the requirements of Rule 112 of these Rules;

(b)

a fire smothering gas installation complying with the requirements of Rule 113 of these Rules;

(c)

a foam fire extinguishing installation complying with the requirements of Rule 114 of these Rules.

If the engine room and boiler rooms are not entirely separated from each other by a bulkhead, or if fuel oil can drain from the boiler room into the engine room, a combined engine and boiler room shall, for the purposes of this paragraph of this Rule, be regarded as a single space.

(7)

In every such vessel in addition to the requirements of paragraph (6) above there shall be provided:—

(a)

if the number of burners in each boiler room is three or more, one foam fire extinguisher of at least 45 litres capacity or a carbon dioxide fire extinguisher of at least 16 kilogrammes capacity. If the number of such burners is less than three there shall be provided for each burner one portable fire extinguisher suitable for extinguishing oil fires;

(b)

in each firing space and in each space which contains any part of any oil fuel installation at least two portable fire extinguishers suitable for extinguishing oil fires, in addition to any which may be carried in compliance with the preceding sub-paragraph;

(c)

in each firing space a receptacle containing 0.3 cubic metres of sand or other dry material suitable for quenching oil fires together with a scoop for its distribution, or alternatively an additional portable fire extinguisher suitable for extinguishing oil fires.

(8)

In every such vessel at least one of the fixed fire extinguishing installations required by paragraph (6) above shall be provided for the protection of any space containing internal combustion type machinery used for main propulsion, or having in the aggregate a total power of not less than 1,000 bhp for auxiliary purposes.

(9)

In every such vessel in addition to the requirements of paragraph (8) above there shall be provided in any such space:—

(a)

one foam fire extinguisher of at least 45 litres capacity or a carbon dioxide fire extinguisher of at least 16 kilogrammes capacity;

(b)

one portable fire extinguisher suitable for extinguishing oil fires for each 1,000 bhp or part thereof of such machinery but in no event less than two such extinguishers, provided that not more than six such extinguishers shall be required in any such space.

(10)

In every such vessel in spaces containing steam turbines or reciprocating steam engines used either for main propulsion or having in the aggregate a total power of not less than 1,000 bhp for auxiliary purposes there shall be provided:—

(a)

foam fire extinguishers each of at least 45 litres capacity or carbon dioxide fire extinguishers each of at least 16 kilogrammes capacity sufficient in number to enable foam or carbon dioxide to be directed on to any part of the lubrication system and on to any part of the casings enclosing pressure lubricated parts of the turbines, engines or associated gearing, if any, provided that such extinguishers shall not be required if equivalent protection is provided in such spaces by a fixed extinguishing installation fitted in compliance with paragraphs (6) or (8) above;

(b)

one portable fire extinguisher for each 1,000 bhp or part thereof of such machinery, suitable for extinguishing oil fires, but in no event less than two such extinguishers, provided that not more than six such extinguishers shall be required in any one such space and provided that such extinguishers shall not be required in addition to any provided in compliance with paragraph (9) above.

(11)

In every such vessel a water spray system, independent of any system fitted in the machinery space and which may be connected to the fire main, shall be fitted in the net store and be operable from outside the store.

(12)

In every such vessel—

(a)

at least two firemen's outfits, which shall comply with the requirements of Rule 115 of these Rules, shall be carried;

(b)

at least one of these outfits shall include a breathing apparatus of the air hose type;

(c)

where firemen's outfits containing only breathing apparatus of the air hose type are carried and an air hose exceeding 36 metres in length would be necessary to reach from the open deck well clear of any hatch or doorway to any part of the accommodation, service, hold or machinery spaces, at least one breathing apparatus of the self-contained type shall also be provided.

(13)

In every such vessel at least one international shore connection complying with the specifications set out in Schedule 19 to these Rules shall be provided, and fixed provision shall be made to enable such a connection to be used on the port side and on the starboard side of the vessel.