Regulation 14 Regulators
No person shall install a primary meter or meter by pass used in connection with a primary meter unless—
there is a regulator controlling the pressure of gas supplied through the meter or the by pass, as the case may be, which provides adequate automatic means for preventing the gas fittings connected to the downstream side of the regulator from being subjected to a pressure greater than that for which they were designed;
where the normal pressure of the gas supply is 75 millibars or more at the inlet to the regulator, there are also adequate automatic means for preventing, in case the regulator should fail, those gas fittings from being subjected to such a greater pressure; and
where the regulator contains a relief valve or liquid seal, such valve or seal is connected to a vent pipe of adequate size and so installed that it is capable of venting safely.
Without prejudice to the requirements of paragraph (1), no person shall cause gas to be supplied from a gas storage vessel to any service pipework or gas fitting unless—
there is a regulator installed which provides adequate automatic means for preventing the installation pipework and gas fittings downstream of the regulator from being subjected to a pressure different from that for which they were designed; and
there is an adequate alternative automatic means for preventing the service pipework from being subjected to a greater pressure than that for which it was designed.
The requirements of paragraph (2)(a) and (b) above shall not apply where the supply of gas—
is from a re-fillable cylinder which is filled other than at the place where it is connected; and
passes through a regulator which controls the nominal operating pressure of that gas.
Where a person installs a regulator for controlling the pressure of gas through a primary meter, a meter by pass used in connection with a primary meter or from a gas storage vessel, or installs a gas appliance itself fitted with a regulator for controlling the pressure of gas to that appliance, he shall immediately thereafter ensure, in either case, that the regulator is adequately sealed so as to prevent its setting from being interfered with without breaking of the seal.
In relation to—
gas from a distribution main, no person except the transporter or a person authorised to act on his behalf; and
gas from a gas storage vessel, no person except the supplier or a person authorised to act on his behalf,
shall break a seal applied under paragraph (4) above.