# The Gas Safety (Installation and Use) Regulations 1994, Regulation 30: Room-sealed appliances


(1) No person shall install a gas appliance in a room used or intended to be used as a bathroom or a shower room unless it is a room-sealed appliance.
(2) No person shall install a gas fire, other gas space heater or a gas water heater of more than 14 kilowatt heat input in a room used or intended to be used as sleeping accommodation unless the appliance is a room-sealed appliance.
(3) No person shall install a gas fire, other gas space heater or a gas water heater of 14 kilowatt heat input or less in a room used or intended to be used as sleeping accommodation unless—
(a) it is a room-sealed appliance; or
(b) it incorporates a safety control designed to shut down the appliance before there is a build up of a dangerous quantity of the products of combustion in the room concerned.

---