Paragraph 2 Non-registration test

Original text. Later amendments are not shown.

Induction meters

(1)

Meters shall be tested to ensure that when the current circuits are open and a voltage of 110% of the marked voltage is applied to the voltage circuits, rotors cease to rotate before completing one complete revolution.

Static meters

(2)

Meters shall be tested for non-registration by one of the following methods–

  • Method 1

    1. (a)
      1. (i)

        When subjected to the test conditions specified in paragraph 2(1), meters shall not emit more than one output pulse over a minimum time period determined in paragraph (ii);

      2. (ii)

        Minimum test period=60000/k minutes, where k=number of pulses per kWh emitted by a meter.

  • Method 2

    1. (b)

      When static meters are fitted with inhibiting circuits, they may be tested for non-registration with a current, which is less than the threshold current in respect of a meter of that type, applied to the current circuits and a voltage of 100% of the marked voltage applied to the voltage circuits of the meters under test. Meters shall not emit more than one output pulse over a minimum time period determined as follows–

      Minimumtestperiod=126000V×I×kminutes

      where V=marked voltage, I=total current and k=number of pulses emitted per kWh by a meter.

  • Method 3

    1. (c)

      The period calculated for Method 1 or Method 2 may be halved, provided that the meters under test do not emit any output pulses during the period of the test.