Paragraph 1 Reports for meters examined and tested
In respect of each meter to which the report refers a statement that–
(a)
the meter referred in the report is accurately described and whether it is a new or repaired meter;
(b)
the meter has been examined and tested in accordance with Schedule 1;
(c)
the uncertainty of measurement was not greater than& ±0.4% at unity power factor or greater than& ±0.6% at 0.5 inductive power factor;
(d)
no meter error was greater than& ±1.5% at any load for single phase meter and polyphase meters on balanced loads;
(e)
the meter did not register when energised on voltage only; and
(f)
paragraph 1(2) of Schedule 1 did or did not apply (as the case may be).