Paragraph 9 Margins of error

Original text. Later amendments are not shown.

(1)

The maximum error permitted for single and polyphase whole current meters and for single and polyphase transformer operated meters, when tested with transformers connected, shall not exceed plus or minus 1.9% for tests 1, 2, 3 and 4 given in Table 2.

(2)

The maximum error permitted for both single phase and polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus or minus 1.4% for tests 1, 2, 3 and 4 given in Table 2.

(3)

For polyphase whole current and transformer operated meters, when tested with transformers connected, the maximum error shall not exceed plus 2% or minus 3% for tests 5 and 6 given in Table 2.

(4)

For polyphase whole current and transformer operated meters, when tested without transformers connected, the maximum error shall not exceed plus 1.5% or minus 2.5% for tests 5 and 6 given in Table 2.

(5)

Where current and voltage transformers, which are intended to be used with meters, are not tested connected to a meter then the total error of the transformers at any load point throughout the rated range shall not exceed 0.5%; unless by matching transformers to meters enables the total error of meter and transformers to meet the requirements of paragraphs 9(1), 9(2), 9(3) and 9(4) above.

TABLE 1

Influence quantitiesReference valueTolerance
Ambient temperatureReference temperature or, if not indicated, 23°C.>15°C to <30°C
Meter positionVertical±3°
VoltageReference voltage±1.5%
FrequencyReference frequency 50Hz±0.5%
Voltage and current waveformSinusoidal formDistortion factor <5%
External magnetic induction at the reference frequency (paragraph 5.4)ZeroInduction value that does not produce a relative error variation of more than& ±0.3%

TABLE 2

Test load in terms of marked current
Test No. & loadPower factorBasic/maximumMaximum continuousLong rangeShort rangeMeter typePolyphase meter load
Note 1 Where a range is given, any value within that inclusive range may be selected.
Note 2 For maximum continuously rated prepayment meters, the low load test value may be twice the value shown.
Note 3 For test no. 4 & 6, the inductive power factor shall be between 0.45 and 0.55 inclusive.
1 (high)1Imax100%100%–200% (Note 1)100%–125% (Note 1)Single & polyphaseBalanced
2 (intermediate)1Ib or 125%IBAny load between 25%–75% of the value specified for Test No. 1Single & polyphaseBalanced
3 (low)15%Ib1.67% (note 2)5%5%Single & polyphaseBalanced
4 (inductive)0.5Ib or Imax100%The same value selected for Test No. 1Single & polyphaseBalanced
5 (element)1Ib100%The same value selected for Test No. 1PolyphaseOne phase loaded in turn
6 (inductive) (element)0.5Ib100%The same value selected for Test No. 1PolyphaseOne phase loaded in turn