# Meters (Certification) Regulations (Northern Ireland) 1998, Paragraph 7: Multi-register meters

Extent: N.I.

Induction meters
(1) (a) All induction meters with more than one register shall be tested on one register in accordance with paragraphs 5 and 6 and on each and every other register at a low load using Method A, Method B or Method C tests and at a high load using Method A test.
(b) For the same load conditions the maximum permitted difference between the error on one register (expressed as a percentage) and the error on any other register (expressed as a percentage) is one.
Static meters
(2) (a) All static meters with more than one register shall be tested on one register in accordance with paragraphs 5 and 6.
(b) For repaired meters with more than one register —
(i) where the total units are the sum of all the registers, a further test shall be carried out on each and every other register using Method A but
(ii) where the total units are recorded on one register, only that register is required to be tested in accordance with paragraphs 5 and 6.

---