# Meters (Certification) Regulations (Northern Ireland) 1998, Paragraph 5

Extent: N.I.

Where a transformer intended for use with a meter has been tested, a statement shall be included in the report that—
(a) the transformer referred to in the report is accurately described and whether it is a new or used transformer;
(b) the transformer has been examined and tested in accordance with Schedule 1 or Harmonisation Documents 553 S2 and 554 S1 approved on 24th March 1992 by the European Committee for Electrotechnical Standardization;
(c) the uncertainty of measurement was not greater than plus or minus 0.1%;
(d) no transformer error was greater than plus or minus 0.5% at any load from 5% to 120% of full load when connected to the maximum rated burden or, if known, the working burden

---