# The Urban Waste Water Treatment (England and Wales) Regulations 1994, Paragraph


Analyses concerning discharges from lagooning shall be carried out on filtered samples; however, the concentration of total suspended solids in unfiltered water samples shall not exceed 150 mg/l.
TABLE 2
REQUIREMENTS FOR DISCHARGES FROM URBAN WASTE WATER TREATMENT PLANTS TO SENSITIVE AREAS WHICH ARE SUBJECT TO EUTROPHICATION AS IDENTIFIED IN SUB-PARAGRAPH (a) OF PART I OF SCHEDULE 1
One or both parameters may be applied depending on the local situation. The values for concentration or for the percentage of reduction shall apply.
{s003} Reduction in relation to the load of the influent.
{s004} Total nitrogen means: the sum of total Kjeldahl-nitrogen (organic N + NH3), nitrate (NO3)-nitrogen and nitrite (NO2)-nitrogen.
Parameters
Concentration
Minimum percentage of reduction {s003}
Reference method of measurement
Total phosphorus
2 mg/l P (10,000—100,000 p.e.) 1 mg/l P (more than 100,000 p.e.)
80
Molecular absorption spectrophotometry
Total nitrogen {s004}
15 mg/l N (10,000—100,000 p.e.) 10 mg/l N (more than 100,000 p.e.)
70—80
Molecular absorption spectrophotometry

---
Source: https://www.legislation.gov.uk/uksi/1994/2841/schedule/3/part/I/paragraph/wrapper5n1 (the official version)
Page: https://openlegislation.uk/urban-waste-water-treatment-england-and-wales-regulations-1994/schedule-3/part-I/paragraph-wrapper5n1
Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives.