# The Water Supply (Water Fittings) Regulations (Northern Ireland) 2009, Paragraph 20

Extent: N.I.

(1) No vent pipe from a primary circuit shall terminate over a storage cistern containing wholesome water for domestic supply or for supplying water to a secondary system.
(2) No vent pipe from a secondary circuit shall terminate over any combined feed and expansion cistern connection to a primary circuit.

---