  "url": "https://openlegislation.uk/water-supply-water-quality-amendment-regulations-2016/schedule-3",
  "json_url": "https://openlegislation.uk/water-supply-water-quality-amendment-regulations-2016/schedule-3.json",
  "legislation": "wsi/2016/410",
  "legislation_title": "The Water Supply (Water Quality) (Amendment) Regulations 2016",
  "legislation_url": "https://openlegislation.uk/water-supply-water-quality-amendment-regulations-2016",
  "path": "schedule/3",
  "kind": "schedule",
  "number": "3",
  "heading": null,
  "text": "“SCHEDULE 5\nMonitoring for indicative dose and analytical performance characteristics\nRegulation 6A\nMonitoring for compliance with the indicative dose\n1. A water undertaker may use reliable screening strategies to indicate the presence of radioactivity in water intended for human consumption.\n2. The strategies referred to in paragraph 1 may include screening for–\n(a) certain radionuclides or individual radionuclide; or\n(b) gross alpha activity or gross beta activity (where appropriate gross beta activity may be replaced by residual beta activity after subtraction of the K-40 activity concentration).\nScreening for certain radionuclides, or screening for an individual radionuclide\n3. If one of the activity concentrations exceeds 20% of the corresponding derived value or the tritium concentration exceeds its parametric value listed in Schedule 2A an analysis of additional radionuclides is required.\n4. A water undertaker must, in deciding which radionuclides require to be measured for each supply, take into account all relevant information about likely sources of radioactivity.\nScreening strategies for gross alpha activity and gross beta activity\n5. Subject to paragraph 6 the recommended screening values are–\n(a) 0,1Bq/l for gross alpha activity; and\n(b) 1,0Bq/l for gross beta activity.\n6. If the gross alpha activity exceeds 0,1Bq/l or the gross beta activity exceeds 1,0Bq/l, analysis for specific radionuclides is required.\n7. The Welsh Ministers may set alternative screening levels for gross alpha activity and gross beta activity where it can be demonstrated by the water undertaker that the alternative levels are in compliance with an indicative dose of 0,1 mSv.\n8. The radionuclides to be measured must be based on all relevant information about likely sources of radioactivity.\nCalculation of the indicative dose\n9. The indicative dose must be calculated from–\n(a) the measured radionuclide concentrations and the dose coefficients laid down in Annex III, Table A of Directive 96/29/Euratom; or\n(b) more recent information recognised by the Welsh Ministers, on the basis of the annual intake of water (730 1 for adults).\n10. Where the following formula is satisfied, it can be assumed that the indicative dose is less than the parametric value of 0,1 mSv and no further investigation is required–\n∑ i=1 n Ci(obs) Ci(der) ≤1 where:\nCi(obs) = observed concentration of radionuclide i\nCi(der) = derived concentration of radionuclide i\nn = number of radionuclides detected.\nDerived concentrations for radioactivity in water intended for human consumption\nOrigin\nNuclide\nDerived concentration\n(1)This table includes values for the most common natural and artificial radionuclides; these are precise values, calculated for a dose of 0,1 mSV, an annual intake of 730 litre and using the dose coefficients laid down in Annex III, Table A of Directive 96/29/ Euratom; derived concentrations for other radionuclides can be calculated on the same basis, and values can be updated on the basis of more recent information recognised by the Welsh Ministers.\n(2)This table allows only for the radiological properties of uranium, not for its chemical toxicity.\nNatural\nU-238\n3,0 Bq/1\nU-234\n2,8 Bq/1\nRa-226\n0,5 Bq/1\nRa-228\n0,2 Bq/1\nPb-210\n0,2 Bq/1\nPo-210\n0,1 Bq/1\nArtificial\nC-14\n240 Bq/1\nSr-90\n4,9 Bq/1\nPu-239/Pu-240\n0,6 Bq/1\nAm-241\n0,7 Bq/1\nCo-60\n40 Bq/1\nCs-134\n7,2 Bq/1\nCs-137\n11 Bq/1\n1-131\n6,2 Bq/1\nPerformance characteristics and methods of analysis\n11. For the following parameters and radionuclides, the method of analysis used must, as a minimum, be capable of measuring activity concentrations with a limit of detection specified below:\nParameters and radionuclides\nLimit of detection (Notes 1,2)\nNotes\nTritium\n10 Bq/1\nNote 3\nRadon\n10 Bq/1\nNote 3\ngross alpha\n0,04 Bq/1\nNote 4\ngross beta\n0,4 Bq/1\nNote 4\nU-238\n0,02 Bq/1\nU-234\n0,02 Bq/1\nRa-226\n0,04 Bq/1\nRa-228\n0,02 Bq/1\nNote 5\nPb-210\n0,02 Bq/1\nPo-210\n0,01 Bq/1\nC-14\n20 Bq/1\nSr-90\n0,4 Bq/1\nPu-239/Pu-240\n0,04 Bq/1\nAm-241\n0,06 Bq/1\nCo-60\n0,5 Bq/1\nCs-134\n0,5 Bq/1\nCs-137\n0,5 Bq/1\nI-131\n0,5 Bq/1\nNote 1: The limit of detection must be calculated according to the ISO standard 11929: Determination of the characteristic limits (decision threshold, detection limit, and limits of confidence interval) for measurements of ionising radiation – Fundamentals and application, with probabilities of errors of 1st and 2nd kind of 0,05 each.\nNote 2: Measurement uncertainties must be calculated and reported as complete standard uncertainties, or as expanded uncertainties with an expansion factor of 1,96 according the ISO Guide for the Expression of Uncertainty in Measurement.\nNote 3: The limit of detection for tritium and for radon is 10% of its parametric value of 100 Bq/1.\nNote 4: The limit of detection for gross alpha activity and gross beta activities are 40% of the screening values of 0,1 and 1,0 Bq/1 respectively.\nNote 5: This limit of detection applies only to initial screening for indicative dose for a new water source; if initial checking indicates that it is not plausible that Ra-228 exceeds 20% of the derived concentration, the limit of detection may be increased to 0,08 Bq/1 for routine Ra-228 nuclide specific measurements, until a subsequent re-check is required.”",
  "extent": "E+W",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "I",
      "label": "I1",
      "text": "Sch. 3 in force at 14.4.2016, see reg. 1(1)"
    },
    {
      "type": "footnote",
      "label": "f1",
      "text": "OJ No. L 159, 29.6.1996, p. 1."
    },
    {
      "type": "footnote",
      "label": "f2",
      "text": "(1)This table includes values for the most common natural and artificial radionuclides; these are precise values, calculated for a dose of 0,1 mSV, an annual intake of 730 litre and using the dose coefficients laid down in Annex III, Table A of Directive 96/29/ Euratom; derived concentrations for other radionuclides can be calculated on the same basis, and values can be updated on the basis of more recent information recognised by the Welsh Ministers."
    },
    {
      "type": "footnote",
      "label": "f3",
      "text": "(2)This table allows only for the radiological properties of uranium, not for its chemical toxicity."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/wsi/2016/410/schedule/3",
    "retrieved_at": "2026-10-28T23:30:19.929139+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}