Schedule 3 SAMPLING FREQUENCIES
TABLE 1:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | ||||
|---|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Reduced | Standard | Increased | ||
| Ground water | Surface water | |||||
| Conductivity or | ≤100 | ≤500 | 4 | 12 | ||
| hydrogen ion | 101– 1000 | 501– 5000 | 4 | 4 | 6 | 12 |
| Odour | 1001– 2000 | 5001–10000 | 4 | 6 | 12 | 24 |
| (qualitative) | 2001– 4000 | 10001–20000 | 6 | 2 | 24 | |
| Taste | 4001– 7000 | 20001–35000 | 11 | 21 | 42 | |
| (qualitative) | 7001–10000 | 35001–50000 | 15 | 30 | 60 | |
TABLE 2:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | ||||
|---|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Reduced | Standard | Increased | ||
| Ground water | Surface water | |||||
| Odour (quantitative) | ||||||
| Taste (quantitative) | ||||||
| Turbidity | ≤100 | ≤500 | 4 | 12 | ||
| Temparture | 101– 1000 | 501– 5000 | 4 | 12 | ||
| Hydrogen ion | 1001– 2000 | 5001–10000 | 4 | 24 | ||
| Nitrate | 2001– 4000 | 10001–20000 | 4 | 4 | 6 | 24 |
| Nitrate | 4001– 7000 | 20001–35000 | 4 | 5 | 10 | 36 |
| Ammonium | 7001–10000 | 35001–50000 | 4 | 5 | 10 | 48 |
| Iron | ||||||
| Aluminium | ||||||
| Manganese | ||||||
| Colour | ||||||
TABLE 3:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | |||
|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Reduced | Standard | Increased | |
| Notes
| |||||
| Trihalomethanes | ≤7000 | ≤35000 | 1 | 4 | 12 |
| Tetrachloromethane | |||||
| Trichloroethene | |||||
| Tetrachloroethene | |||||
| Copper | |||||
| Lead | 7001–10000 | 35001–50000 | 1 | 4 | 24 |
| Zinc | |||||
| Pesticides(i) | |||||
| Polycyclic aromatic hydrocarbons(ii) | |||||
TABLE 4:
Sampling frequencies at consumers' taps
| Parameters | Sampling Frequency(number per annum) | |
|---|---|---|
| Standard | Increased | |
| Chloride | ||
| Sulphate | ||
| Calcium | ||
| Magnesium | ||
| Sodium | ||
| Potassium | ||
| Dry residues | ||
| Oxidizability (permanganate value) | ||
| Total organic carbon | ||
| Boron | ||
| Surfactants | ||
| Phosphorus | 1 | 12 |
| Fluoride | ||
| Barium | ||
| Silver | ||
| Arsenic | ||
| Cadmium | ||
| Cyanide | ||
| Chromium | ||
| Mercury | ||
| Nickel | ||
| Antimony | ||
| Selenium | ||
| Total hardness | ||
| Alkalinity | ||
TABLE 5:
Sampling frequencies at supply points
| Water Supply Zone or Combination of Zones | Sampling Frequency (number per annum) | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Table 1 Parameters | Table 2 Parameters | Table 3 Parameters | Table 4 Parameters | ||||||||||||
| Reduced | Standard | Increased | Reduced | Standard | Increased | Reduced | Standard | Increased | Reduced | Standard | Increased | ||||||
| GW | SW | GW | SW | GW | SW | GW | SW | ||||||||||
| |||||||||||||||||
| ≤100 | ≤500 | 4 | 12 | 4 | 12 | 1 | 2 | 4 | 12 | 1 | 12 | ||||||
| 101– 1000 | 501– 5000 | 4 | 4 | 6 | 12 | 4 | 12 | 1 | 2 | 4 | 12 | 1 | 12 | ||||
| 1001– 2000 | 5001– 10000 | 4 | 6 | 12 | 24 | 4 | 24 | 1 | 2 | 4 | 12 | 1 | 12 | ||||
| 2001– 4000 | 10001– 20000 | 6 | 12 | 24 | 4 | 4 | 6 | 24 | 1 | 2 | 4 | 12 | 1 | 12 | |||
| 4001– 10000 | 20001– 50000 | 15 | 30 | 60 | 4 | 5 | 10 | 60 | 1 | 2 | 4 | 12 | 1 | 12 | |||
| 10001– 20000 | 50001– 100000 | 30 | 60 | 120 | 5 | 10 | 20 | 60 | 2 | 3 | 6 | 24 | 1 | 1 | 2 | 24 | |
| 20001– 30000 | 100001– 150000 | 45 | 90 | 180 | 8 | 15 | 30 | 60 | 2 | 3 | 6 | 24 | 1 | 2 | 3 | 24 | |
| 30001– 60000 | 150001– 300000 | 90 | 180 | 360 | 15 | 30 | 60 | 120 | 2 | 3 | 6 | 24 | 2 | 3 | 6 | 24 | |
| 60001–100000 | 300001– 500000 | 90 | 180 | 360 | 30 | 60 | 120 | 3 | 5 | 10 | 24 | 3 | 5 | 10 | 24 | ||
| 100001–200000 | 500001–1000000 | 90 | 180 | 360 | 30 | 60 | 120 | 5 | 10 | 20 | 36 | 5 | 10 | 20 | 36 | ||
TABLE 6:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | |
|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Standard | |
| Total coliforms } | ≤100 | ≤500 | 12 |
| Faecal coliforms } | 101–1000 | 501– 5000 | 12 |
| Residual disinfectant } | 1001–2000 | 5001–10000 | 24 |
| Colony counts } | 2001–4000 | 10001–20000 | 48 |
| 20001–50000 | at the rate of 12 per 5000 population except in the case of colony counts where the standard number is 5. | ||
TABLE 7:
Sampling frequencies for treatment works
| Parameters | Volume of water supplied (m3/d) for domestic purposes | Sampling frequency (number per annum) | |
|---|---|---|---|
| Reduced | Standard | ||
1 Total and faecal coliforms, | ≤2000 | 12 | 52 |
| residual disinfectant and colony counts | 2001–6000 | 52 | 104 |
2 Total and faecal coliforms | 6001–12000 | 104 | 208 |
| and residual disinfectant | >12000 | 104 | 365 |
3 Colony counts | >6000 | 52 | 104 |