1.
Ammonium
0.50
mgNH4/l
Consumers' taps
2.
Chloride
250
mgCl/l
Supply point
3.
Clostridium perfringens (including spores)
0
Number/100ml
Supply point
4.
Coliform bacteria
0
Number/100ml
Consumers' taps
5.
Colony counts
No abnormal change
Number/1ml at 22°C
Consumers' taps, service reservoirs and treatment works
5.
Colony counts
No abnormal change
Number/1ml at 37°C
Consumers' taps, service reservoirs and treatment works
6.
Conductivity
2500
μS/cm at 20°C
Supply point
7.
Sulphate
250
mgSO4/l
Supply point
8.
Total indicative dose (for radioactivity)
0.10
mSv/year
Supply point
9.
Total organic carbon (TOC)
No abnormal change
mgC/l
Supply point
10.
Tritium (for radioactivity)
100
Bq/l
Supply point
11.
Turbidity
1
NTU
Treatment works

---