Schedule 2 SAMPLING FREQUENCIES
TABLE 1:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | ||||
|---|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Reduced | Standard | Increased | ||
| Ground water | Surface water | |||||
| Conductivity or | ≤100 | ≤500 | 4 | 12 | ||
| hydrogen ion | 101-1000 | 501-5000 | 4 | 4 | 6 | 12 |
| Odour | 1001-2000 | 5001-10000 | 4 | 6 | 12 | 24 |
| (qualitative) | 2001-4000 | 10001-20000 | 6 | 12 | 24 | |
| Taste | 4001-7000 | 20001-35000 | 11 | 21 | 42 | |
| (qualitative) | 7001-10000 | 35001-50000 | 15 | 30 | 60 | |
TABLE 2:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | ||||
|---|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Reduced | Standard | Increased | ||
| Ground water | Surface water | |||||
| Odour | ||||||
| (quantitative) | ||||||
| Taste | ||||||
| (qualitative) | ||||||
| Turbidity | ≤100 | ≤500 | 4 | 12 | ||
| Temperature | 101-1000 | 501-5000 | 4 | 12 | ||
| Hydrogen ion | 1001-2000 | 5001-10000 | 4 | 24 | ||
| Nitrate | 2001-4000 | 10001-20000 | 4 | 4 | 6 | 24 |
| Nitrite | 4001-7000 | 20001-35000 | 4 | 5 | 10 | 36 |
| Ammonium | 7001-10000 | 35001-50000 | 4 | 5 | 10 | 48 |
| Ammonium | ||||||
| Iron | ||||||
| Aluminium | ||||||
| Manganese | ||||||
TABLE 3:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | |||
|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Reduced | Standard | Increased | |
| Notes | |||||
(i) ie any fungicide, herbicide or insecticide; increased or reduced sampling, where required or permitted, may be confirmed to the substance in question. | |||||
(ii) The sum of the detected concentrations of fluoranthene, benzo 3.4 fluoranthene, benzo 11.12 fluoranthene, benzo 3.4 pyrene, benzo 1.12 perylene and indeno (1,2,3-cd) pyrene. | |||||
| Trihalomethanes | ≤7000 | ≤3500 | 1 | 4 | 12 |
| Tetrachloromethane | |||||
| Trichloroethene | |||||
| Tetrachloroethene | |||||
| Copper | |||||
| Lead | 7001-10000 | 35001-50000 | 1 | 4 | 24 |
| Zinc | |||||
| Pesticidesf1 | |||||
| Polycyclic aromatic hydrocarbonsf2 | |||||
TABLE 4:
Sampling frequencies at consumers' taps
| Parameters | Sampling Frequency | |
|---|---|---|
| (number per annum) | ||
| Standard | Increased | |
| Chloride | ||
| Sulphate | ||
| Calcium | ||
| Magnesium | ||
| Sodium | ||
| Potassium | ||
| Dry residues | ||
| Oxidizability | ||
| (permanganate value) | ||
| Total organic carbon | ||
| Boron | ||
| Surfactants | ||
| Phosphorus | 1 | 12 |
| Fluoride | ||
| Barium | ||
| Silver | ||
| Arsenic | ||
| Cadmium | ||
| Cyanide | ||
| Chromium | ||
| Mercury | ||
| >Nickel | ||
| Antimony | ||
| Selenium | ||
| Total hardness | ||
| Alkalinity | ||
TABLE 5:
Sampling frequencies at supplyh points
| Water Supply Zone or Combination of Zones | Sampling Frequency (number per annum) | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Table 1f3 Parameters | Table 2 Parameters | Table 3 Parameters | Table 4 Parameters | ||||||||||||
| Reduced | Standard | Increased | Reduced | Standard | Increased | Reduced | Standard | Increased | Reduced | Standard | Increased | ||||||
| GW | SW | GW | SW | GW | SW | GW | SW | ||||||||||
| GW = Ground water SW = Surface water | |||||||||||||||||
* Reference is to Tables 1 to 4 of this Schedule | |||||||||||||||||
| ≤100 | ≤500 | 4 | 12 | 4 | 12 | 1 | 2 | 4 | 12 | 1 | 12 | ||||||
| 101-1000 | 501-5000 | 4 | 4 | 6 | 12 | 4 | 12 | 1 | 2 | 4 | 12 | 1 | 12 | ||||
| 1001-2000 | 5001-10000 | 4 | 6 | 12 | 24 | 4 | 24 | 1 | 2 | 4 | 12 | 1 | 12 | ||||
| 2001-4000 | 10001-20000 | 6 | 12 | 24 | 4 | 4 | 6 | 24 | 1 | 2 | 4 | 12 | 1 | 12 | |||
| 4001-10000 | 20001-50000 | 15 | 30 | 60 | 4 | 5 | 10 | 60 | 1 | 2 | 4 | 12 | 1 | 12 | |||
| 1001-20000 | 50001-100000 | 30 | 60 | 120 | 5 | 10 | 20 | 60 | 2 | 3 | 6 | 24 | 1 | 1 | 2 | 24 | |
| 20001-30000 | 100001-150000 | 45 | 90 | 180 | 8 | 15 | 30 | 60 | 2 | 3 | 6 | 24 | 1 | 2 | 3 | 24 | |
| 30001-60000 | 150001-300000 | 90 | 180 | 360 | 15 | 30 | 60 | 120 | 2 | 3 | 6 | 24 | 2 | 3 | 6 | 24 | |
| 60001-100000 | 300001-500000 | 90 | 180 | 360 | 30 | 60 | 120 | 3 | 5 | 10 | 24 | 3 | 5 | 10 | 24 | ||
| 100001-200000 | 500001-1000000 | 90 | 180 | 360 | 30 | 60 | 120 | 5 | 10 | 20 | 36 | 5 | 10 | 20 | 36 | ||
TABLE 6:
Sampling frequencies at consumers' taps
| Parameters | Water Supply Zone | Sampling Frequency (number per annum) | |
|---|---|---|---|
| Volume distributed (m3/d) for domestic purposes | Population Supplied | Standard | |
| Total Coliforms | ≤100 | ≤500 | 12 |
| Faecal coliforms | 101-1000 | 501-5000 | 12 |
| Residual disinfectant | 1001-2000 | 5001-10000 | 24 |
| Colony counts | 2001-4000 | 10001-20000 | 48 |
| 20001-50000 | at the rate of 12 per 5000 population except in the case of colony counts where the standard number is 52 | ||
TABLE 7:
Sampling frequencies for treatment works
| Parameters | Volume of water supplied (m3/d) for domestic purposes | Sampling frequency (number per annum) | |
|---|---|---|---|
| Reduced | Standard | ||
| 1. Total and faecal coliforms, | ≤2000 | 12 | 52 |
| residual disinfectant and | 2001-6000 | 52 | 104 |
| colony counts | |||
| 2. Total and faecal coliforms | 6001-12000 | 104 | 208 |
| and residual disinfectant | >12000 | 104 | 365 |
| 3. Colony counts | >6000 | 52 | 104 |
Annotations
Footnotes
- f1
(i)
ie any fungicide, herbicide or insecticide; increased or reduced sampling, where required or permitted, may be confirmed to the substance in question.
- f2
(ii)
The sum of the detected concentrations of fluoranthene, benzo 3.4 fluoranthene, benzo 11.12 fluoranthene, benzo 3.4 pyrene, benzo 1.12 perylene and indeno (1,2,3-cd) pyrene.
- f3
*
Reference is to Tables 1 to 4 of this Schedule