Paragraph 6.10 MeteringF1
Every building must be designed and constructed in such a way that each F2building, or part of a building designed for different occupation is fitted with fuel F3and power meters.
Limitation
This standard does not apply to–
communal areas of buildings in different occupation;
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
heating fired by solid fuel or biomass; or
heating for individual dwellings fired by LPG or oil.