Regulation 5 Minimum performance criteria for methods of analysisI1
Northern Ireland
The Department shall ensure that—
(a)
the minimum performance criteria for all methods of analysis applied are based on uncertainty of measurement of 50% or below (k = 2) estimated at the level of relevant environmental quality standards and a limit of quantification equal or below a value of 30% of the relevant environmental quality standards; and
(b)
in the absence of relevant environmental quality standard for a given parameter, or in the absence of a method of analysis meeting the minimum performance criteria set out in paragraph (a), that monitoring is carried out using best available techniques not entailing excessive costs.