Paragraph 3 Quantities which may be emitted
(1)
Subject to the provisions of paragraph 4 below, the quantities of grit and dust, in pounds per hour, which may be emitted by the chimney of a schedule 1 furnace the heat output of which is within the highest and lowest values specified in column (1) of the following table shall not exceed—
(a)
if the furnace burns solid matter, the quantities prescribed in column (2) against the value representing the output of that furnace or
(b)
if the furnace burns liquid matter, the quantities prescribed in column (3) against that value.
| Maximum Continuous Rating in pounds of steam per hour (from and at 100°C. (212°F.)) or in thousands of British thermal units per hour | Maximum permitted quantities of grit and dust in pounds per hour | |
|---|---|---|
| Furnaces burning solid matter | Furnaces burning liquid matter | |
| (1) | (2) | (3) |
| 825 | 1.10 | 0.25 |
| 1,000 | 1.33 | 0.28 |
| 2,000 | 2.67 | 0.56 |
| 3,000 | 4.00 | 0.84 |
| 4,000 | 5.33 | 1.12 |
| 5,000 | 6.67 | 1.4 |
| 7,500 | 8.50 | 2.1 |
| 10,000 | 10.00 | 2.8 |
| 15,000 | 13.33 | 4.2 |
| 20,000 | 16.67 | 5.6 |
| 25,000 | 20.0 | 7.0 |
| 30,000 | 23.4 | 8.4 |
| 40,000 | 30 | 11.2 |
| 50,000 | 37 | 12.5 |
| 100,000 | 66 | 18 |
| 150,000 | 94 | 24 |
| 200,000 | 122 | 29 |
| 250,000 | 149 | 36 |
| 300,000 | 172 | 41 |
| 350,000 | 195 | 45 |
| 400,000 | 217 | 50 |
| 450,000 | 239 | 54.5 |
| 475,000 | 250 | 57 |