Part III CONTAINMENT MEASURES FOR INDUSTRIAL PROCESSES
| Containment measures | Containment levels | ||
|---|---|---|---|
| 2 | 3 | 4 | |
1 Viable micro-organisms should be contained in a system which physically separates the process from the environment (closed system). | Yes | Yes | Yes |
2 Exhaust gases from the closed system should be treated so as to— | Minimise release | Prevent release | Prevent release |
3 Sample collection, addition of materials to a closed system and transfer of viable micro-organisms to another closed system, should be performed so as to— | Minimise release | Prevent release | Prevent release |
4 Bulk culture fluids should not be removed from the closed system unless the viable micro-organisms have been— | Inactivated by validated means | Inactivated by validated chemical or physical means | Inactivated by validated chemical or physical means |
5 Seals should be designed so as to— | Minimise release | Prevent release | Prevent release |
6 Closed systems should be located within a controlled area— | Optional | Optional | Yes, and purpose-built |
(a) biohazard signs should be posted; | Optional | Yes | Yes |
(b) access should be restricted to nominated personnel only; | Optional | Yes | Yes, via air-lock |
(c) personnel should wear protective clothing; | Yes, work clothing | Yes | Yes, a complete change |
(d) decontamination and washing facilities should be provided for personnel; | Yes | Yes | Yes |
(e) personnel should shower before leaving the controlled area; | No | Optional | Yes |
(f) effluent from sinks and showers should be collected and inactivated before release; | No | Optional | Yes |
(g) the controlled area should be adequately ventilated to minimise air contamination; | Optional | Optional | Yes |
(h) the controlled area should be maintained at an air pressure negative to atmosphere; | No | Optional | Yes |
(i) input and extract air to the controlled area should be HEPA filtered; | No | Optional | Yes |
(j) the controlled area should be designed to contain spillage of the entire contents of closed system; | Optional | Yes | Yes |
(k) the controlled area should be sealable to permit fumigation. | No | Optional | Yes |
7 Effluent treatment before final discharge. | Inactivated by validated means | Inactivated by validated chemical or physical means | Inactivated by validated physical means |