Paragraph 3 Energy efficiency requirements for motors
IE is set out in Tables 21 to 26, for different values of the motor rated output power PN at 50 Hz or 60 Hz.
IE classes are determined at rated output power (PN), rated voltage (UN), and based on 25 °C ambient reference temperature.
For 50/60 Hz motors, the requirements in Tables 21 to 26 must be met at both 50Hz and 60 Hz at the rated output power specified for 50 Hz.
For 50Hz motors the requirements in Tables 21 to 23 must be met at 50 Hz at the rated output power specified for 50 Hz.
For 60Hz motors the requirements in Tables 24 to 26 must be met at 60 Hz at the rated output power specified for 60 Hz.
Losses must be determined in accordance with Schedule 17.
Table 21
Minimum efficiencies (ηn) for IE2 efficiency level at 50 Hz (per cent)
| Rated output power PN[kW] | 2 poles | 4 poles | 6 poles | 8 poles |
|---|---|---|---|---|
| 0.12 | 53.6 | 59.1 | 50.6 | 39.8 |
| 0.18 | 60.4 | 64.7 | 56.6 | 45.9 |
| 0.20 | 61.9 | 65.9 | 58.2 | 47.4 |
| 0.25 | 64.8 | 68.5 | 61.6 | 50.6 |
| 0.37 | 69.5 | 72.7 | 67.6 | 56.1 |
| 0.40 | 70.4 | 73.5 | 68.8 | 57.2 |
| 0.55 | 74.1 | 77.1 | 73.1 | 61.7 |
| 0.75 | 77.4 | 79.6 | 75.9 | 66.2 |
| 1.1 | 79.6 | 81.4 | 78.1 | 70.8 |
| 1.5 | 81.3 | 82.8 | 79.8 | 74.1 |
| 2.2 | 83.2 | 84.3 | 81.8 | 77.6 |
| 3 | 84.6 | 85.5 | 83.3 | 80.0 |
| 4 | 85.8 | 86.6 | 84.6 | 81.9 |
| 5.5 | 87.0 | 87.7 | 86.0 | 83.8 |
| 7.5 | 88.1 | 88.7 | 87.2 | 85.3 |
| 11 | 89.4 | 89.8 | 88.7 | 86.9 |
| 15 | 90.3 | 90.6 | 89.7 | 88.0 |
| 18.5 | 90.9 | 91.2 | 90.4 | 88.6 |
| 22 | 91.3 | 91.6 | 90.9 | 89.1 |
| 30 | 92.0 | 92.3 | 91.7 | 89.8 |
| 37 | 92.5 | 92.7 | 92.2 | 90.3 |
| 45 | 92.9 | 93.1 | 92.7 | 90.7 |
| 55 | 93.2 | 93.5 | 93.1 | 91.0 |
| 75 | 93.8 | 94.0 | 93.7 | 91.6 |
| 90 | 94.1 | 94.2 | 94.0 | 91.9 |
| 110 | 94.3 | 94.5 | 94.3 | 92.3 |
| 132 | 94.6 | 94.7 | 94.6 | 92.6 |
| 160 | 94.8 | 94.9 | 94.8 | 93.0 |
| 200 up to 1,000 | 95.0 | 95.1 | 95.0 | 93.5 |
Table 22
Minimum efficiencies (ηn) for IE3 efficiency level at 50 Hz (per cent)
| Rated output power PN[kW] | 2 poles | 4 poles | 6 poles | 8 poles |
|---|---|---|---|---|
| 0.12 | 60.8 | 64.8 | 57.7 | 50.7 |
| 0.18 | 65.9 | 69.9 | 63.9 | 58.7 |
| 0.20 | 67.2 | 71.1 | 65.4 | 60.6 |
| 0.25 | 69.7 | 73.5 | 68.6 | 64.1 |
| 0.37 | 73.8 | 77.3 | 73.5 | 69.3 |
| 0.40 | 74.6 | 78.0 | 74.4 | 70.1 |
| 0.55 | 77.8 | 80.8 | 77.2 | 73.0 |
| 0.75 | 80.7 | 82.5 | 78.9 | 75.0 |
| 1.1 | 82.7 | 84.1 | 81.0 | 77.7 |
| 1.5 | 84.2 | 85.3 | 82.5 | 79.7 |
| 2.2 | 85.9 | 86.7 | 84.3 | 81.9 |
| 3 | 87.1 | 87.7 | 85.6 | 83.5 |
| 4 | 88.1 | 88.6 | 86.8 | 84.8 |
| 5.5 | 89.2 | 89.6 | 88.0 | 86.2 |
| 7.5 | 90.1 | 90.4 | 89.1 | 87.3 |
| 11 | 91.2 | 91.4 | 90.3 | 88.6 |
| 15 | 91.9 | 92.1 | 91.2 | 89.6 |
| 18.5 | 92.4 | 92.6 | 91.7 | 90.1 |
| 22 | 92.7 | 93.0 | 92.2 | 90.6 |
| 30 | 93.3 | 93.6 | 92.9 | 91.3 |
| 37 | 93.7 | 93.9 | 93.3 | 91.8 |
| 45 | 94.0 | 94.2 | 93.7 | 92.2 |
| 55 | 94.3 | 94.6 | 94.1 | 92.5 |
| 75 | 94.7 | 95.0 | 94.6 | 93.1 |
| 90 | 95.0 | 95.2 | 94.9 | 93.4 |
| 110 | 95.2 | 95.4 | 95.1 | 93.7 |
| 132 | 95.4 | 95.6 | 95.4 | 94.0 |
| 160 | 95.6 | 95.8 | 95.6 | 94.3 |
| 200 up to 1,000 | 95.8 | 96.0 | 95.8 | 94.6 |
Table 23
Minimum efficiencies (ηn) for IE4 efficiency level 50 Hz (per cent)
| Rated output power PN[kW] | 2 poles | 4 poles | 6 poles | 8 poles |
|---|---|---|---|---|
| 0.12 | 66.5 | 69.8 | 64.9 | 62.3 |
| 0.18 | 70.8 | 74.7 | 70.1 | 67.2 |
| 0.20 | 71.9 | 75.8 | 71.4 | 68.4 |
| 0.25 | 74.3 | 77.9 | 74.1 | 70.8 |
| 0.37 | 74.3 | 77.9 | 74.1 | 70.8 |
| 0.40 | 78.9 | 81.7 | 78.7 | 74.9 |
| 0.55 | 81.5 | 83.9 | 80.9 | 77.0 |
| 0.75 | 83.5 | 85.7 | 82.7 | 78.4 |
| 1.1 | 85.2 | 87.2 | 84.5 | 80.8 |
| 1.5 | 86.5 | 88.2 | 85.9 | 82.6 |
| 2.2 | 88.0 | 89.5 | 87.4 | 84.5 |
| 3 | 89.1 | 90.4 | 88.6 | 85.9 |
| 4 | 90.0 | 91.1 | 89.5 | 87.1 |
| 5.5 | 90.9 | 91.9 | 90.5 | 88.3 |
| 7.5 | 91.7 | 92.6 | 91.3 | 89.3 |
| 11 | 92.6 | 93.3 | 92.3 | 90.4 |
| 15 | 93.3 | 93.9 | 92.9 | 91.2 |
| 18.5 | 93.7 | 94.2 | 93.4 | 91.7 |
| 22 | 94.0 | 94.5 | 93.7 | 92.1 |
| 30 | 94.5 | 94.9 | 94.2 | 92.7 |
| 37 | 94.8 | 95.2 | 94.5 | 93.1 |
| 45 | 95.0 | 95.4 | 94.8 | 93.4 |
| 55 | 95.3 | 95.7 | 95.1 | 93.7 |
| 75 | 95.6 | 96.0 | 95.4 | 94.2 |
| 90 | 95.8 | 96.1 | 95.6 | 94.4 |
| 110 | 96.0 | 96.3 | 95.8 | 94.7 |
| 132 | 96.2 | 96.4 | 96.0 | 94.9 |
| 160 | 96.3 | 96.6 | 96.2 | 95.1 |
| 200 up to 249 | 96.5 | 96.7 | 96.3 | 95.4 |
| 250 up to 314 | 96.5 | 96.7 | 96.5 | 95.4 |
| 315 up to 1,000 | 96.5 | 96.7 | 96.6 | 95.4 |
Table 24
Minimum efficiencies (ηn) for IE2 efficiency level at 60 Hz (per cent)
| Rated output power PN [kW] | Number of poles | |||
|---|---|---|---|---|
| 2 | 4 | 6 | 8 | |
| 2 | 4 | 6 | 8 | |
| 0.12 | 59.5 | 64.0 | 50.5 | 40.0 |
| 0.18 | 64.0 | 68.0 | 55.0 | 46.0 |
| 0.25 | 68.0 | 70.0 | 59.5 | 52.0 |
| 0.37 | 72.0 | 72.0 | 64.0 | 58.0 |
| 0.55 | 74.0 | 75.5 | 68.0 | 62.0 |
| 0.75 | 75.5 | 78.0 | 73.0 | 66.0 |
| 1.1 | 82.5 | 84.0 | 85.5 | 75.5 |
| 1.5 | 84.0 | 84.0 | 86.5 | 82.5 |
| 2.2 | 85.5 | 87.5 | 87.5 | 84.0 |
| 3.7 | 87.5 | 87.5 | 87.5 | 85.5 |
| 5.5 | 88.5 | 89.5 | 89.5 | 85.5 |
| 7.5 | 89.5 | 89.5 | 89.5 | 88.5 |
| 11 | 90.2 | 91.0 | 90.2 | 88.5 |
| 15 | 90.2 | 91.0 | 90.2 | 89.5 |
| 18.5 | 91.0 | 92.4 | 91.7 | 89.5 |
| 22 | 91.0 | 92.4 | 91.7 | 91.0 |
| 30 | 91.7 | 93.0 | 93.0 | 91.0 |
| 37 | 92.4 | 93.0 | 93.0 | 91.7 |
| 45 | 93.0 | 93.6 | 93.6 | 91.7 |
| 55 | 93.0 | 94.1 | 93.6 | 93.0 |
| 75 | 93.6 | 94.5 | 94.1 | 93.0 |
| 90 | 94.5 | 94.5 | 94.1 | 93.6 |
| 110 | 94.5 | 95.0 | 95.0 | 93.6 |
| 150 | 95.0 | 95.0 | 95.0 | 93.6 |
| 185 | 95.4 | 95.4 | 95.0 | 93.6 |
| 220 | 95.4 | 95.4 | 95.0 | 93.6 |
| 250 | 95.4 | 95.4 | 95.0 | 93.6 |
| 300 | 95.4 | 95.4 | 95.0 | 93.6 |
| 335 | 95.4 | 95.4 | 95.0 | 93.6 |
| 375 up to 1000 | 95.4 | 95.8 | 95.0 | 94.1 |
Table 25
Minimum efficiencies (ηn) for IE3 efficiency level at 60 Hz (per cent)
| Rated output power PN [kW] | Number of poles | |||
|---|---|---|---|---|
| 2 | 4 | 6 | 8 | |
| 2 | 4 | 6 | 8 | |
| 0.12 | 62.0 | 66.0 | 64.0 | 59.5 |
| 0.18 | 65.6 | 69.5 | 67.5 | 64.0 |
| 0.25 | 69.5 | 73.4 | 71.4 | 68.0 |
| 0.37 | 73.4 | 78.2 | 75.3 | 72.0 |
| 0.55 | 76.8 | 81.1 | 81.7 | 74.0 |
| 0.75 | 77.0 | 83.5 | 82.5 | 75.5 |
| 1.1 | 84.0 | 86.5 | 87.5 | 78.5 |
| 1.5 | 85.5 | 86.5 | 88.5 | 84.0 |
| 2.2 | 86.5 | 89.5 | 89.5 | 85.5 |
| 3.7 | 88.5 | 89.5 | 89.5 | 86.5 |
| 5.5 | 89.5 | 91.7 | 91.0 | 86.5 |
| 7.5 | 90.2 | 91.7 | 91.0 | 89.5 |
| 11 | 91.0 | 92.4 | 91.7 | 89.5 |
| 15 | 91.0 | 93.0 | 91.7 | 90.2 |
| 18.5 | 91.7 | 93.6 | 93.0 | 90.2 |
| 22 | 91.7 | 93.6 | 93.0 | 91.7 |
| 30 | 92.4 | 94.1 | 94.1 | 91.7 |
| 37 | 93.0 | 94.5 | 94.1 | 92.4 |
| 45 | 93.6 | 95.0 | 94.5 | 92.4 |
| 55 | 93.6 | 95.4 | 94.5 | 93.6 |
| 75 | 94.1 | 95.4 | 95.0 | 93.6 |
| 90 | 95.0 | 95.4 | 95.0 | 94.1 |
| 110 | 95.0 | 95.8 | 95.8 | 94.1 |
| 150 | 95.4 | 96.2 | 95.8 | 94.5 |
| 185 | 95.8 | 96.2 | 95.8 | 95.0 |
| 220 | 95.8 | 96.2 | 95.8 | 95.0 |
| 250 | 95.8 | 96.2 | 95.8 | 95.0 |
| 300 | 95.8 | 96.2 | 95.8 | 95.0 |
| 335 | 95.8 | 96.2 | 95.8 | 95.0 |
| 375 up to 1000 | 95.8 | 96.2 | 95.8 | 95.0 |
Table 26
Minimum efficiencies (ηn) for IE4 efficiency level at 60 Hz (per cent)
| Rated output power PN [kW] | Number of poles | |||
|---|---|---|---|---|
| 2 | 4 | 6 | 8 | |
| 2 | 4 | 6 | 8 | |
| 0.12 | 66.0 | 70.0 | 68.0 | 64.0 |
| 0.18 | 70.0 | 74.0 | 72.0 | 68.0 |
| 0.25 | 74.0 | 77.0 | 75.5 | 72.0 |
| 0.37 | 77.0 | 81.5 | 78.5 | 75.5 |
| 0.55 | 80.0 | 84.0 | 82.5 | 77.0 |
| 0.75 | 82.5 | 85.5 | 84.0 | 78.5 |
| 1.1 | 85.5 | 87.5 | 88.5 | 81.5 |
| 1.5 | 86.5 | 88.5 | 89.5 | 85.5 |
| 2.2 | 88.5 | 91.0 | 90.2 | 87.5 |
| 3.7 | 89.5 | 91.0 | 90.2 | 88.5 |
| 5.5 | 90.2 | 92.4 | 91.7 | 88.5 |
| 7.5 | 91.7 | 92.4 | 92.4 | 91.0 |
| 11 | 92.4 | 93.6 | 93.0 | 91.0 |
| 15 | 92.4 | 94.1 | 93.0 | 91.7 |
| 18.5 | 93.0 | 94.5 | 94.1 | 91.7 |
| 22 | 93.0 | 94.5 | 94.1 | 93.0 |
| 30 | 93.6 | 95.0 | 95.0 | 93.0 |
| 37 | 94.1 | 95.4 | 95.0 | 93.6 |
| 45 | 94.5 | 95.4 | 95.4 | 93.6 |
| 55 | 94.5 | 95.8 | 95.4 | 94.5 |
| 75 | 95.0 | 96.2 | 95.8 | 94.5 |
| 90 | 95.4 | 96.2 | 95.8 | 95.0 |
| 110 | 95.4 | 96.2 | 96.2 | 95.0 |
| 150 | 95.8 | 96.5 | 96.2 | 95.4 |
| 185 | 96.2 | 96.5 | 96.2 | 95.4 |
| 220 | 96.2 | 96.8 | 96.5 | 95.4 |
| 250 | 96.2 | 96.8 | 96.5 | 95.8 |
| 300 | 96.2 | 96.8 | 96.5 | 95.8 |
| 335 | 96.2 | 96.8 | 96.5 | 95.8 |
| 375 up to 1000 | 96.2 | 96.8 | 96.5 | 95.8 |