(1)

Article 25 (voltage stability requirements applicable to AC-connected offshore power park modules) is amended as follows.

(2)

Omit paragraph 2.

(3)

In paragraph 3—

(a)

omit the words from “Notwithstanding the provisions” to “Continental Europe synchronous area”;

(b)

for Table 10 substitute—

“

Table 10

Synchronous areaVoltage rangeTime period for operation
Great Britain0.90 pu – 1.10 pu where the voltage base for pu values is below 300kVUnlimited
0.90 pu – 1.05 pu where the voltage base for pu values is from 300kV to 400kVUnlimited
1.05 pu – 1.10 pu where the voltage base for pu values is from 300kV to 400kv15 minutes

”

(4)

In paragraph 5, for Table 11 substitute—

“

Table 11

Parameters for Figure 8

Synchronous areaMaximum range of Q/PmaxMaximum range of steady-state voltage level in PU
Great Britain0, at the offshore connection point for configuration 1 (as described in Article 23(3)(a)).0.225
0.33, at the offshore connection point for configuration 2 (as described in Article 23(3)(b)).0.225

”