Paragraph 19
(1)
Article 25 (voltage stability requirements applicable to AC-connected offshore power park modules) is amended as follows.
(2)
Omit paragraph 2.
(3)
In paragraph 3—
(a)
omit the words from “Notwithstanding the provisions” to “Continental Europe synchronous area”;
(b)
for Table 10 substitute—
“
Table 10
Synchronous area Voltage range Time period for operation Great Britain 0.90 pu – 1.10 pu where the voltage base for pu values is below 300kV Unlimited 0.90 pu – 1.05 pu where the voltage base for pu values is from 300kV to 400kV Unlimited 1.05 pu – 1.10 pu where the voltage base for pu values is from 300kV to 400kv 15 minutes ”
(4)
In paragraph 5, for Table 11 substitute—
“
Table 11
Parameters for Figure 8
Synchronous area Maximum range of Q/Pmax Maximum range of steady-state voltage level in PU Great Britain 0, at the offshore connection point for configuration 1 (as described in Article 23(3)(a)). 0.225 0.33, at the offshore connection point for configuration 2 (as described in Article 23(3)(b)). 0.225 ”