Paragraph 17 Control of noise during operation

Original text. Later amendments are not shown.

(1)

No part of numbered works 1, 2 or 3 is to commence until a noise mitigation scheme containing details of how the design of that numbered work has ensured that rating noise levels for normal mode of operation predicted at 1m from the façade of noise sensitive receptors as included Table 1 below will not be exceeded for that part, has been submitted to and approved by the relevant planning authority.

(2)

The noise mitigation scheme must also include a set of noise limits that must not be exceeded during operation at locations that are 5m from the equipment listed below, such locations to be agreed with the relevant planning authority in the noise mitigation scheme. The equipment referred to in this sub-paragraph are—

(a)

flue gas booster fans;

(b)

carbon dioxide compressor buildings;

(c)

pumps; and

(d)

combined power turbine buildings.

(3)

The noise mitigation scheme must be implemented and maintained as approved pursuant to sub-paragraph (1).

Table 1

Operational Rating Noise Limits

(1)

Receptor

(2)

Easting

(3)

Northing

(3)

Rating Level, LAR,Tr dB

R1, Wren Hall467273.9427168.230
R2, Long Drax468163.8428107.525
R3, Old Lodge467515.8428113.324
R4, Drax Abbey Farm467042.9428281.226
R5, Foreman’s Cottage466842.8428479.726
R6, 2 Forest Grove Barlow465213.8428417.734
R7, Brigg Lane465054.1426248.033
R8, Station Cottage466671.9426399.023
R9, Briden Bungalow467759.4426857.727
R10, Weston House466922.8426331.124
R11, Rose Cottage468427.5426135.424
R12, Brigg Farm Court465207.2426066.824
R13, Camela House464868.2426604.736
R14, Low Farm464211.5427351.135