Regulation 4 Amendment of regulation 4I1
Northern Ireland
In regulation 4—
in paragraph (1), for “, (3)”, substitute “to (3C)”;
for paragraph (3), substitute—
“(3)Paragraph (3A) applies to a transformer in respect of which it is reasonable to assume that it contains—
(a)0.005% by weight, or less, of PCBs within the fluids containing PCBs; or
(b)a total volume of 0.05dm3, or less, of fluids containing PCBs.
(3A)A transformer to which this paragraph applies—
(a)may be held until the end of its useful life; and
(b)must then be decontaminated in accordance with paragraph (4)(b) to (d), or disposed of, as soon as possible.
(3B)Paragraph (3C) applies to a transformer in respect of which it is reasonable to assume that it contains—
(a)more than 0.005% but no more than 0.05% by weight of PCBs within the fluids containing PCBs; and
(b)a total volume of more than 0.05dm3 of PCBs fluids containing PCBs.
(3C)A transformer to which this paragraph applies—
(a)may be held until the end of 31st December 2025; and
(b)must then be decontaminated in accordance with paragraph (4)(b) to (d), or disposed of, as soon as possible.”
in paragraph (4)(a), for “less than 0.05% by weight and, if possible, to no more than 0.005% by weight” substitute “0.005% by weight, or less, or to reduce the total volume of fluids containing PCBs to 0.05dm3, or less”.
In regulation 4(8)—
in sub-paragraph (a), for “, (3)” substitute “to (3C)”;
in sub-paragraphs (b) and (c), for “not contaminated”, in both places it occurs, substitute “relevant”;
after paragraph (8) insert—
“(9)In paragraph (8), “relevant equipment” means any equipment (including any capacitor or receptacle containing residual stocks) which—
(a)contains PCBs; or
(b)having contained PCBs, has not been decontaminated, other than one which contains a total volume of PCBs exceeding 0.05dm3.
(10)For the purposes of paragraph (9)—
(a)the PCB volume of a power capacitor shall be measured by reference to all of the separate elements of a combined set; and
(b)anything of a type which may contain PCBs shall be treated as containing PCBs unless it is reasonable to assume the contrary.”
Annotations
Commencement
- I1
Reg. 4 in operation at 17.6.2025, see reg. 1(1)