Division 5 Products for use in ventilation systems (excluding smoke and heat exhaust ventilation)
United Kingdom
Original text. Later amendments are not shown.
| Applies to | ventilation ducts |
| Standard(s) | EN 13501-3; EN 1366-1 |
| Classification: |
| EI | 15 | 20 | 30 | 45 | 60 | 90 | 120 | 180 | 240 | |
| E | | | 30 | | 60 | | | | | |
| Notes | The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. The addition of the symbol ‘S’ indicates the satisfaction of an extra restriction on leakage. |
| Applies to | fire dampers |
| Standard(s) | EN 13501-3; EN 1366-2 |
| Classification: |
| EI | 15 | 20 | 30 | 45 | 60 | 90 | 120 | 180 | 240 | |
| E | | | 30 | | 60 | 90 | 120 | | | |
| Notes | The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbolts ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. The addition of the symbol ‘S’ indicates the satisfaction of an extra restriction on leakage. |