Division 4 Non-loadbearing elements or parts of works and products therefor

United Kingdom

Original text. Later amendments are not shown.

F1For cavity barriers this standard is complemented by EOTA TR 031.

Applies to partitions (including partitions incorporating uninsulated portions, and cavity barriers)
Standard(s) EN13501-2; EN 1364-1 f1 ; EN 1992-1-2; EN 1993-1-2; EN 1994-1-2; EN 1995-1-2; EN 1996-1-2; EN 1999-1-2
Classification: -
E 20 30 60 90 120
EI 15 20 30 45 60 90 120 180 240
EI-M 30 60 90 120 180 240
EW 20 30 60 90 120
Notes —
Applies toceilings with independent fire resistance
Standard(s)EN 13501-2; EN 1364-2
Classification:
EI1530456090120180240
NotesThe classification is completed by ‘(a → b)’, ‘(b → a)’, or ‘(a ↔ b)’ to indicate whether the element has been tested and fulfils the requirements from above or below only or both.
Applies tofacades (curtain walls) and external walls (including glazed elements)
Standard(s)EN 13501-2; EN 1364-3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2
Classification:
E15306090120
EI15306090120
EW203060
Notes

The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both.

Where required, mechanical stability means that there are no falling parts liable to cause personal injury during the time for the E or EI classification.

Applies toraised floors
Standard(s)EN 13501-2; EN 1366-6
Classification:
R1530
RE30
REI30
NotesThe classification is completed by the addition of the suffix ‘f’ to indicate full fire resistance or ‘r’ to indicate exposure to the reduced constant temperature exposure only.
Applies topenetration seals and linear gap seals
Standard(s)EN 13501-2; EN 1366-3,4
Classification:
E1530456090120180240
EI152030456090120180240
Notes—

The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.

Applies tofire doors and shutters (including those that incorporate glazing and hardware) and their closing devices
Standard(s)EN 13501-2; EN 1634-1
Classification:
E152030456090120180240
EI152030456090120180240
EW203060
NotesThe I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) f2.

The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.

Applies tosmoke control doors
Standard(s)EN 13501-2; EN 1634-3
Classification: S200 or Sa depending upon the test conditions fulfilled
NotesThe addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) f3.

The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.

Applies toclosures for conveyers and trackbound transportation systems
Standard(s)EN 13501-2; EN 1366-7
Classification:
E1530456090120180240
EI152030456090120180240
EW203060
Notes F2The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. An I classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) f4.
Applies toservice ducts and shafts
Standard(s)EN 13501-2; EN 1366-5
Classification:
E152030456090120180240
EI152030456090120180240
NotesThe classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use.
Applies tochimneys
Standard(s)EN 13501-2; EN 13216
Classification: G + distance in mm (e.g. G 50)
NotesDistance not required for built-in products.
Notes

The suffixes ‘ 1 ’ and ‘ 2 ’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification.

Applies to Wall and ceiling coverings
Standard(s) EN 13501-2; EN 14135
Classification:
K 1 10
K 2 10 30 60

Annotations

Textual amendments

F1

Substituted by Commission Decision of 11 April 2011 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, construction works and parts thereof (notified under document C(2011) 2417) (Text with EEA relevance) (2011/232/EU).

F2

Substituted by Commission Decision of 27 August 2003 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, as regards the inclusion of smoke and heat control products (notified under document number C(2003) 2851) (Text with EEA relevance) (2003/629/EC).

Footnotes

f1

For cavity barriers this standard is complemented by EOTA TR 031.

f2

The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.

f3

The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.

f4

The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.